Cla-Val X105L/X105L2 User Manual

Limit switch assemblies, Model, Installation typical application

Advertising
background image

Limit Switch Assemblies

Switches shown in
unactivated position.

CLA-VAL

124-02/624-02

Float Valve

Annunciator
Alarm

Stilling Well

Tank

Supply

Double Pole Double Throw Switch

Single Pole Double Throw Switch

Installation

Typical Application

Actuating Collar Adjustment

Minimum Setting

When adjusting actuating collar for proper switch
action, a clearance of at least 1/16" (1/8” for 24”
valve) must be provided between the collar and
the bushing gland nut when valve is in the fully
closed position.

Used for any electrical operation which can be
performed by either opening or closing a switch;
such as alarm systems, process control, pump
control, motor starting or stopping, etc. Readily
attached to most Cla-Val Valves.

1. Remove plug in top of

valve cover.

2. Screw actuating stem

into main valve stem.

3. Slip adapter down

over stem and screw
into place on valve
cover.

4. Attach micro switch

housing and bracket to
adapter with jam nut.

5. Bring electrical supply

circuit into unit through
the 1/2" tapping in
micro switch housing.

6. Adjust switch collars.

(Set collar to trip
switch after valve is
positioned fully open
or fully closed)

• UL Listed Switches
• Positive Action
• Rugged and Dependable
• Weather Proof or Explosion Proof
• Easy To Adjust

The Cla-Val Model X105L/X105L2 Limit Switch Assembly is a
rugged, dependable and positive acting switch assembly actuated
by the opening or closing of a Cla-Val control valve on which it is
mounted. The single pole, double throw micro switch can be
connected either to open or to close an electrical circuit when
actuated. By loosening the allen screw on the actuating collar and
raising or lowering the collar on the stem, the X105L is easily
adjusted to signal that the valve has fully reached the desired
position (open or closed).

X105L

X105L2

MODEL

COM

N.C.

N.O.

Circuit Diagram
of Single Pole
Double Throw
Switch

Common
Lug

Normally
Closed

Normally
Open

N.C.

N.C.

N.O.

COM

COM

Circut Diagram
of Single Pole
Double Throw
Switch

Normally
Closed

Normally
Open

Common Lug

N.O.

Stem

Bushing Gland Nut

Jam Nut

Bracket

Switch Actuating Collar

Adapter

Min.
1/16"

Switch only

Annunciator
Alarm

Advertising