Features

Alarm -

Programmed to signal when system conditions exceed a desired

value or in the event of a system component failure. It can be configured
to be latching or non-latching, normally open or normally closed contact
with deadbands.

Absolute Alarm

- Activates when the process variable exceeds

alarm set-point. It can be either high and/or low acting.
Deviation Alarm

- Shifts as the set-point is changed. It can be

symmetrical or asymmetrical.
Fault Alarm

- Activates when the process variable is lost.

Set-Point Rate of Change

- Prevents accidental or sudden changes in

the programmed set-point. It is also invaluable when used on high differential
or surge sensitive applications where valve speed of operation must be
tightly controlled.

Process Variable Backup

- Can automatically recognize secondary

process variable or can be programmed to open or close valve or can
default to backup pilot system using alarm function.

DC Power Supply

- Provides source of power for signal transmitter.

Retransmission

- Transmit process variable or set-point values.

Offsets

- Adjusts the process variable and remote set point settings if

respective signals do not match.

Filter

- Stabilizes process variable signal when required.

Security System

- Prevents unauthorized changes.

Input Linearization

- For flow measurement across orifices, venturies, etc.

Digital Inputs

- Selects specific set-points. (optional)

NEMA 4X Enclosure

(optional)

Input Signals

The 131VC-1 Electronic Control System is designed to accept
industry standard 4-20 mA full scale signals for pressure, flow or
level control from customer supplied transmitter(s).

Flow Measurement

using a differential signal requires activating

the square root extractor to obtain direct flow readout.

Modulating Level Control

requires the use of an optional X117

Valve Position Transmitter in addition to a level transmitter.

Valve Position Control

requires an optional X117 Valve Position

Transmitter installed on the valve.

Other configurations are available on a special order basis, consult
the factory for details.

Specifications

Control Input:

4-20 mA full scale (others optional)

Control Parameters

Proportional Bands:

1 to 999%, settable in 0.1%

increments independently for opening and closing

Deadbands:

achievable up to 15% of input range

Cycle Time:

1 to 120 seconds in 1 sec. increments.

Environmental Parameters

Temperature:

0°C to 50°C (32°F to 1 22°F)

Humidity:

10 to 90%, non-condensing

Power Consumption

15 watts Max. at 120 VA, 50160 Hz

Voltage and Frequency

Universal power supply: 90 to 250 VAC, 48 to 62 Hz.
24 to 30 volts AC or DC, +/- 5%.

Noise Immunity

Common mode rejection (process input)

: >120 db.

Normal mode rejection (process input):

>80 db.

AC line is double filtered and transient protected.
Snubbers are provided for each relay output.

Construction

Case:

extruded, non-perforated black anodized

aluminum with ABS plastic sleeve.
Bezel: Black plastic ABS.
Chassis assembly: plug-in type.
Keys: Silicone rubber with diffusion printed graphics.
NEMA rating: front panel conforms to NEMA 4X when
instrument is properly installed.

Agency Approvals

Memory Retention

Lithium battery maintains all programming for approximately
ten years.

Security

There are two levels of access: restricted and full. A
configurable code is used to enter the full access level.
Functions not available in the restricted level are configurable.

LISTED

Process Control Equipment

4N66

UL

®

LR 84603