Cla-Val 134-05 User Manual

Solenoid operated deluge valve, Model, Schematic diagram

Advertising
background image

Solenoid Operated Deluge Valve

C

V

Factor

Valve Size

Globe

Pattern

Angle

Pattern

Inches

mm.

Gal./Min. (gpm.)

Litres/Sec. (l/s.)

Gal./Min. (gpm.)
Litres/Sec. (l/s.)

3

80

115

27.6

139

33.4

4

100

200

48

240

58

6

150

440

105.6

541

130

8

200

770

184.8

990

238

10

250

1245

299

1575

378

Functional Data

Schematic Diagram

Item Description

1

100G/2100G UL Listed Hytrol Main Valve

2

CS3 Solenoid Control

3

100-01 Hytrol Pilot Valve

4

X58C Restriction Orifice

5

X46A Flow Clean Strainer

2

4

3

F

INDEPENDENT

OPERATING

PRESSURE

5

1

INLET

OUTLET

CS3

3

2

1

Cover Capacity

Specifications

SIZES

Globe: 3” - 10” flanged
Angle: 3” - 10” flanged

END DETAILS

Ductile Iron 150 ANSI B16.42 flanged

Cast Steel 150 ANSI B16.5 flanged

PRESSURE RATINGS

150 class, 250 psi maximum (Ductile Iron)
150 class, 285 psi maximum (All other materials)
300 class, 300 psi maximum (All materials)

TEMPERATURE RANGE

Water: to 180° F. Max

MATERIALS

Main valve body & cover:

Ductile Iron ASTM A-536*

Cast Steel ASTM A216-WCB*

Naval Bronze ASTM B61

Nickel Aluminum Bronze ASTM B148

Super Duplex Stainless Steel

Stainless Steel ASTM A743-CF-8M

Main valve trim:
Bronze / Stainless Steel

Pilot control system:

Cast Bronze ASTM B62

UL Listed 3" - 10"

• U.L. Listed / U.L.C. Listed

• Fast Acting Solenoid Control
• Reliable Drip Tight Shut-off
• Simple Design, Proven Reliable
• Easy Installation & Maintenance

The Cla-Val Model 134-05 Solenoid Control Valve is an
on-off control valve which either opens or closes upon receiving
an electrical signal to the solenoid pilot control. This valve consists
of a 100G/2100G U.L. listed hytrol main valve, a three-way solenoid valve
and an auxiliary pilot valve. This pilot control system alternately applies
pressure to/or relieves pressure from the diaphragm chamber of the main
valve. It is furnished either normally open (de-energize solenoid to open)
or normally closed (energize solenoid to open).

Note: For seawater applications use 100GS/2100GS main valve

Valve

Size

Displace-

ment

3”

.080 gal

4”

.169 gal

6”

.531 gal

8”

1.26 gal

10”

2.51 gal

134-05