Installing the alarm & float switch, Figure b figure a figure c – Liberty Pumps ALM-2-1 User Manual

Page 2

Advertising
background image

INSTALLING THE ALARM & FLOAT SWITCH

1. Determine indoor mounting location for alarm.
2. Insert screw (supplied) at desired wall location.

Note: Screw is to be located over wall stud or used with
a wall anchor sized for a #8 x 1.25" self tapping screw.

3. Hang alarm using keyhole on back of enclosure. Install

second screw in mounting fl ange located on bottom of
alarm.

4. Make sure power to alarm is disconnected.
5. Place the fl oat switch cord into the clamp as shown in

Figure A.

6. Locate the clamp at the desired activation level and secure

the clamp to the discharge pipe as shown in Figure A.

Note: Do not install cord under hose clamp.
7. Tighten the hose clamp using a screwdriver. Over tightening

may result in damage to the plastic clamp. Make sure the
fl oat cable is not allowed to touch the excess hose clamp
band during operation.

Note: All hose clamp components are made of 18-8

stainless steel material. See your Liberty Pumps

®

supplier

for replacements.

8. Bring cable leads back to alarm and wire according to

Figure B. A cord bung is included with the kit.

Note: When used with a pump application, connect alarm
to a circuit separate from the pump circuit. This allows the
alarm to operate if the pump circuit fails.

9. Open battery door and install 9 VDC alkaline battery (not

included). Battery must be installed for backup alarm
to function. Note:
The green power on light does not
come on when unit is on battery power.

10. Plug the alarm in to apply primary power. Verify that the

green "power on" light illuminates.

11. Check installation by manually tipping the fl oat. The horn

will sound and the "alarm" light should come on.

12. Press "silence" button to silence the horn. The horn will

silence while the red "alarm" light stays on.

13. Tip fl oat back down and press "test" button. The "alarm"

light and horn will activate.

14. Test unit once a week. Replace battery every 12 months

and after each alarm condition to ensure proper
operation. If battery is low, low battery chirp feature will
cause the horn to chirp approximately once per minute.
Replace battery when this happens.

15. Using the provided cable clasp, secure cord to outlet as

shown in Figure C. Use existing receptacle faceplate screw
and supplied washer.

16. Test unit once per week to insure proper operation.

Figure B

Figure A

Figure C

For detailed specifi cations on this product, or for the complete line of

Liberty Pumps

®

products, visit our web site at www.libertypumps.com.

ELECTRICAL SHOCK HAZARD

Disconnect power before installing or servicing this
product. A qualifi ed service person must install and
service this product according to applicable electrical
and plumbing codes.

EXPLOSION OR FIRE HAZARD

Do not use this product with fl ammable liquids.
Do not install in hazardous locations as defi ned by
National Electrical Code, ANSI/NFPA 70.

Failure to follow these precautions could result in serious injury or death. Replace product immediately if switch cable becomes damaged

or severed. Keep these instructions with warranty after installation. This product must be installed in accordance with National Electric Code, ANSI/

NFPA 70 so as to prevent moisture from entering or accumulating within boxes, conduit bodies, fi ttings, fl oat housing, or cable.

7000 Apple Tree Avenue

Bergen, New York 14416 USA

Phone: 1-800-543-2550

www.libertypumps.com

©SJE-Rhombus 06/12

Instl. Instr. PN 1017740D

Model TAAB

7299000A

Advertising
This manual is related to the following products: