6 register block overview, 7 nmtc configuration register block, Register block overview – IMP Pumps NMTC module User Manual

Page 33: Nmtc configuration register block .33

Advertising
background image

33

NOTE:

Any branch/derivative cable is considered unterminated. Keep them short, below 250m

combined for maximum speed and reliability.

7.6 Register block overview

NMTC Modbus RTU registers are grouped in the following register blocks:

Start

address

Register block

Readable/Writeable Description

001

NMTC

configuration

R/W

Configuration of the NMTC

module.

021

NMTC status

R

Status registers for the NMTC

module.

101

Pump control

R/W

Pump control registers.

201

Pump status

R

Status data from the pump.

301

Pump data

R

Measured data from the pump.

All addresses contain 16 bit (one Word) registers. Some are bit interpreted while others are
combined for a 32 bit value.

NOTE: All register addresses are 1-based. Address 001 is thus transmitted over bus as 0x0000.

7.7 NMTC Configuration register block

Registers in this block are read with either function codes 0x03 or 0x04. They can be written as
holding registers with function codes 0x06 and 0x10.

NOTE:

All values in this block are stored in nonvolatile memory immediately after write.

NOTE:

See section “4.3 Module mode selection” an use Mode 8 or 9 to restore default settings if

you cannot access the controller after writing to these registers.