6 manifolds setup programming 6, Manifolds menu 6, 6manifolds setup programming – Franklin Fueling Systems Tank Sentinel (TS-1001, 2001, 504, & 508) Setup Programming Guide User Manual

Page 46: Manifolds menu

Advertising
background image

Manifolds Setup

Page

6 - 1

6

6

Manifolds SETUP PROGRAMMING

Manifolds Menu

NOTE

Press the

DOWN

key

See the Table of Contents to find topics in
this manual. See the Preface for general
information about this manual. And see the
Installation, Operator’s, TroubleShooting
Guides, and Application Notes for other
reference material.

Contents:
Manifolds Menu
Manifold Data Menu
Manifold Alarms Menu
Worksheet 6-1 – Manifolds
1 thru 4

SELECT MENU OPTION

SETUP

UPGRADE LANGUAGE

DATALOG

M1

M2

M3

M4

SETUP MENU

(MORE)

EXIT

SYSTEM

TANKS

PROBES

SETUP MENU

(MORE)

PRODUCTS

MANIFOLDS

REPORTS

LK TSTS

M1

M2

M3

M4

MANIFOLDS

DATA

ALARMS

M1

M2

M3

M4

H

U

MENU

×

Press this key and follow the

7

highlighted sequence below

*

This menu appears only after a MANIFOLD

has been selected from the TANK – DATA –
MANIFOLD

menu.

Manifolds are used to physically connect tanks
together and to expand the total capacity by the
sum of all tanks connected (see next page).

Tanks that are physically manifolded must:
1) have identical product (programmed here for

manifold tanks)

2) use the same manifold number ( 1, 2, 3 or 4 )

...ref. Chapter 2 (TANKS – DATA – TANK N
– MANIFOLD menu).

Manifold numbers must not be reused to connect
different (other) tanks & products.

Example:

Tanks 1, 2 & 3 contain 87 Octane

gasoline and are physically manifold together
and each are programed to use Manifold #1.
Tanks 4 & 5 store 93 Octane gas and are
manifold together with Manifold #2.

All tanks

that are physically manifold together must
use the same (logical) manifold number
.

MANIFOLD DATA

Press (

M

) key to select MAN 1-4 to

MAN 1

setup.

:

(manifolds 3 & 4 available with TS-2001/508 only)

MAN 4

MANIFOLD DATA N

N = manifold number (1 or 2, or 1 thru 4)

COPY

(Optional - used to copy manifold data) Press

M1

key.

COPY FROM MANIFOLD DATA X TO N

MAN 1

Press (

M

) key to select a manifold to copy data from.

:

MAN 4

COPY MANIFOLD DATA X TO N
PRESS ENTER IF YOU ARE SURE?

Press

ENTER

to accept this data.