3
Electrical Wiring
The connectors ship with the units but are not connected
to either the controller or sensor. The installer must make
up both ends of the connection once both components are
installed.
Note: Make sure that the wires on the top and bottom are
connected to the same pin number.
1. Prepare wires by removing cable covering 1.6”
(40 mm) from the end.
0.14 – 0.34 mm²
26 – 22 AWG
40 mm
1.6"
Figure 3: Prepare Wiring Connector
Note: Do not strip wire insulation
2. Insert the wires into the connector.
Figure 4: Insert Wires
3. Bend wires over clips as shown.
Figure 5: Bend Wires Over Clips
4. Trim wires so they don’t protrude past the clips.
3.5 – 6.0 mm
0.14 – 0.25"
Figure 6: Trim Wires
5. Insert connector into plug and twist it to lock.
1.2 Nm
0.88 lb-ft
Figure 7: Tighten Connector
6. Test the unit.