Electrical Wiring

The connectors ship with the units but are not connected

to either the controller or sensor. The installer must make

up both ends of the connection once both components are

installed.

Note: Make sure that the wires on the top and bottom are

connected to the same pin number.

1. Prepare wires by removing cable covering 1.6”

(40 mm) from the end.

0.14 – 0.34 mm²

26 – 22 AWG

40 mm

1.6"

Figure 3: Prepare Wiring Connector

Note: Do not strip wire insulation

2. Insert the wires into the connector.

Figure 4: Insert Wires

3. Bend wires over clips as shown.

Figure 5: Bend Wires Over Clips

4. Trim wires so they don’t protrude past the clips.

3.5 – 6.0 mm

0.14 – 0.25"

Figure 6: Trim Wires

5. Insert connector into plug and twist it to lock.

1.2 Nm

0.88 lb-ft

Figure 7: Tighten Connector

6. Test the unit.