9

Shown installed in Curv Radial Lens at left.
For specific in-product placement in other Alera Lighting products, see individual product specification
and/or technical data sheets. For special placement requests, contact Alera Lighting.

To adjust light level setting, twist sensor as
indicated by arrow and seen below.

installed sensor option

dspl—daylight sensor, philips luxsense

requires Mark 7 dimming Ballast, 0-10v • up to 32% potential energy savings

LuxSense Commissioning
• Measure the light level under each LuxSense sensor with no or negligible daylight contribution

— Light meter required

• If needed, turn the sensor until the required light level is reached (with no or negligible daylight contribution)
• Duplicate this in other rooms when similar daylight and reflectance conditions exist
• Note that Philips LuxSense is not designed for maintaining a constant light level

Warning: The reduced light level should be no more than 30% lower than the average installed light level, without

daylight contributions (example: 55fc installed, adjustment down to 39fc is possible)
Optical Characteristics
• It is assumed that the reflection in a room is such that a light level of 45fc on a table (2.6' high) will result in 2.3fc seen
by the controller at 8' under a viewing angle of 45°; the opening angle can be adapted by the sensor ring control,
realizing an adjustment factor between 1⁄3 and 3.
Controls Characteristics
• LuxSense compensates approximately for 50% of the added light (simulated and measured with a fluorescent
light source). See graph at left below. In case of a natural light source, the compensation is higher than 50%.