Alera Lighting APCS OS User Manual

A+class, Occupancy sensor, Technical installation data

Advertising
background image

Page 1/5 Rev. 07/16/13 H72-00436

IntegRated ContRols / A+CLASS

APCS OS TID

A+CLASS

OCCupAnCy SenSOr

Technical Installation Data

© 2013 alera lighting, a division of Hubbell lighting, Inc. Because of continuing product improvement programs, alera lighting reserves the right to change specifications
without notice. 701 Millennium Blvd. greenville, sC 29607 / tel 864.678.1000 / Website www.aleralighting.com

US Patent #8,436,542

32'

44'

Major motion will

turn lights ON

~1,200 ft

2

32'

23'

45'

64'

Major motion will

hold lights ON

~2,400 ft

2

Minor motion will

hold lights ON

~1,000 ft

2

Description

The A+ClAss™ ceiling-mounted occupancy sensor combines ultrasonic (Us) and passive infrared (PIR) technologies to turn lighting on and off
based on occupancy. The sensor features Hubbell’s patented IntelliDAPT™ technology, which makes all the sensor’s adjustments automatically.
Throughout the product’s lifespan, smart software analyzes the controlled area and makes digital adjustment to sensitivity and timer settings
providing maintenance-free “Install and Forget” operation.

precAUtions

• CAUTION: FOR USE WITH CLASS 2, LOW VOLTAGE SYSTEMS ONLY. DO NOT USE IN HIGH VOLTAGE APPLICATIONS.
• Read and understand all instructions before beginning installation.
• NOTICE: For installation by a licensed electrician in accordance with National and/or local Electrical Codes.
• NOTICE: For indoor use only.
• CAUTION: USE COPPER CONDUCTOR ONLY.
• Confirm device ratings are suitable for application prior to installation. Use of device in applications beyond its specified ratings or in

applications other than its intended use may cause an unsafe condition and will void manufacturer’s warranty.

• NOTICE: Do not install if any damage to product is noticed.

occUpAncy sensor coverAge AnD plAcement

• The sensor must have an unobstructed view of the room. Do not mount behind or near tall cabinets, shelves, hanging fixtures, etc.
• Keep the sensor away from air flow – at least 8 feet from HVAC vents.
• Place the sensor 8-10 ft. away from doorway – pointing towards doorway for optimal occupant detection.
• Closely follow the diagrams for major and minor motion coverage.
• Decrease total coverage area by 15% for “soft” rooms (for example, heavy draperies or heavy carpeting).
• Indicated range is when unit is mounted on ceilings 8'-12' in height. sensor should not be mounted on ceilings above 12'.