Doc. #: 0260011-J0 Rev B

64

6.4  Rectifier Module

Figure 50 shows the

Cordex 48-1.8kW can be used in the AMS24 HP systems to provide battery charging

thumbscrew latch that secures the rectifier into the shelf. During normal operation the rectifier is

locked into position. A handle (or grip) is incorporated into the front panel to facilitate the removal of

the rectifier from the shelf. No special tools are required.

Figure 50 — Cordex 48-1.8kW

LEDs

Thumbscrew

Latch

Handle

6.4.1  Front Panel LEDs

Rectifier status summary

The three LEDs on the front panel show the rectifier alarm, communication fail, and rectifier on/off

status.

AC ON The top green LED illuminates when the AC input voltage is within its allowable range. The LED flashes

(~2Hz) when input voltage is outside the allowable range. The AC input voltage is invalid if the AC Mains

Low or AC Mains High alarm is active. The LED extinguishes if the AC input fails.

DC ON The middle green LED illuminates when the rectifier is delivering power to the load. The LED flashes

when communication is lost. The LED extinguishes when the rectifier is off, e.g., when commanded by

the CXC.

ALARM The bottom red LED illuminates during an active Module Fail alarm if the module is unable to source

power as a result of any of the following conditions:

Output fuse blown

AC mains input fail

Module fail (ramp test fail)

High voltage (OVP) shutdown

Thermal shutdown

Local shutdown

UPF fail

No output power

Fan fail