Alpha Technologies AMPS80 HP User Manual

Page 111

Advertising
background image

109

Doc. #: 026-069-B0 Rev F

10.5 Alarm Settings (ID 551-950)

Global Parameters (ID: 551-600)

;551;

;Alarm on prog. relay (255 is NU);

;255; ; ;

x

Replace 255 by the Alarm Code you wish for programming the relay user selectable 3

x

See previous codes for the T2S and Enclosed list for the TSI.

;553;;

;MAJ relay temporization;

;60; ;sec;

x

Temporization of Urgent alarm (from 0 to 65536 sec)

;554;

;MIN relay temporization;

;30; ;sec;

x

High DC voltage – a higher value re-starts the DC/AC converter

;556;

;Saturation alarm threshold;

;100; ;%;

x

Level of load that generates an alarm indicating there is a risk of overload.

x

This parameter takes into account the redundancy defined previously

x

I.e. P ex : system with 4 modules with 1 redundant –> 80 % of 3 modules

;558;

;AC

in

is present (1:true 0:false);

;1; ; ;

x

Allow to inhibit the alarm when ACin not Present

x

1 –> gives alarm when main Network is not Present

x

0 –> no alarm when main Network is not Present (AC in not available or Regular inverter)

;570;

;Log near. full thresh. (100-200);

;180; ; ;

x

Number of messages in the Logfile. It is from the Logfile that alarm is generated when the

Logfile is about completed.

Configuration of types of Alarms

- Alarm Type (ID : 601 - 900) : Minor(1) - Major(2) - No Alarm(0)

x

Choice for type of alarms as detailed hereafter

x

No Alarm = 0 / Minor = 1 / Major = 2

;828;

;227.DIG INP1 FAILURE;

;0; ; ;

x

Type of alarms for Digital inlet 1 (Inlet to be configured by user)