Alpha Technologies CFR 1500, CFR 1500RM User Manual

Page 5

Advertising
background image

THE ALPHA CFR

i

IMPORTANT:

EMERGENCY SHUTDOWN PROCEDURE ON INSIDE BACK COVER

Table Of Contents

The Alpha CFR1500 and CFR 1500 RM

Uninteruptible Power Supplies

1.

INTRODUCTION ............................................................................ 1
1.1

The Alpha CFR

1

1.2

The CFR Advantage

2

1.3

Unpacking and Inspection

4

2.

FEATURES .................................................................................... 5
2.1

A Tour of the CFR

5

2.2

The CFR Front Panel

5

2.3

CFR Rear Panel

6

2.4

Information Management Options

8

Standard Interface Device
Intelligent Interface Device
External Modem

2.5

Communication / Interface Options

10

2.6

RS-232 Communication Options

15

RS–232 Connector
Rear Panel RS–232 Port
Terminal Emulation Setup
Connecting an External Modem
Desktop IID RS–232 Por t

3.

INSTALLATION ........................................................................... 18
3.1

Pre-Installation

18

Site Preparation
Utility Circuit Breaker
Grounding
Standby Generators

3.2

Connecting the CFR (Plug and receptacle)

19

3.2.1

Terminal Block Input and Output Wiring

20

3.3

External Battery Pack

22

3.4

208 VAC vs 240 VAC (60 Hz) Configurations

23

4.

OPERATION ................................................................................ 26
4.1

Start-up, Test and Shutdown

26

4.2

External Modem Configuration

29

Specifications
Enabling External Modem
Configuring the modem to work with CFR

74

7.1

Specifications

,

continued

Common Specifications

Input Frequency

60 Hz or 50 Hz (± 3%)

Input Voltage Variation

- 20% to + 10%

Output Frequency

± 0.1 Hz (inverter mode)

Output Regulation

± 1%

Efficiency @Typical Load

90%

Total Harmonic Distortion

< 5%

Output Waveform

Sine

Step Load Response

< 10% @ 100% load

Noise Attenuation

Common Mode

-120dB (100K - 1 MHz)

Normal Mode

-60dB (100K - 1 MHz)

Low Voltage Trigger

80% nominal voltage (adjustable)

High Voltage Trigger

110% nominal voltage (adjustable)

Batteries

Valve regulated, maintenance-free

Battery Voltage

48 VDC

Batt. Low Volt. Cutout

39 VDC (>25% load), [42 VDC (<25% load)]

Battery Recharge Time

5.0 hrs.

Charger

Linear

(3 A max.)

Charger Voltage

55.2 VDC at 25°C (adjustable)

Operating Temp

32°-104° F / 0°-40°C

Heat Output

574 BTU/h; 168 W

Audible Noise @ 1M

CFR 1500

< 40dBA

CFR 1500RM

< 50 dBA

Indicators

Line Present, Line Failure,
Low Battery Shutdown,
Low Battery Warning (LED / audible alarm),
Test, Service and Output Load

Controls

Manual Start / Test, Alarm OFF

Connectors

AC Input, AC Output, External Alarm;
Intelligent Interface Device and
External Battery

Output Alarms

Rear panel RJ-45 connector (Form C
contact closures rated 1A, 30 V) for
Line Present / Line Failure, and
Battery OK / Low Battery Warning

Specifications subject to shange without notice

7. SPECIFICATIONS