4 alarm monitoring, 1 factory preset alarm table, Alarm monitoring – Alpha Technologies Cordex CXCRF 48-300W User Manual

Page 40: Factory preset alarm table

Advertising
background image

0300072-J0 RevA

Page 36 of 46

4.4 Alarm Monitoring

4.4.1 Factory Preset Alarm Table

Table 7 contains the default alarms in the MCU.

ID

Description

Relay

1

2

3

4

1.

DC Bus Extra Low

X

2.

DC Bus Low

X

3.

DC Bus High

X

4.

DC Bus Extra High

X

5.

DC Bus Voltage Sense Failure

X

6.

Mains Failure

X

7.

Mains Partial Failure

X

8.

Mains Low

X

9.

Not used

10.

One rectifier Failure

X

11.

More than One Rectifier Failure

X

12.

Missing Rectifier (with Comp@s)

X

13.

Battery Last Test Failed

X

14.

Battery on discharge

X

15.

Not used

16.

Not used

17.

Battery LVD relay Open

X

18.

Bat. Temperature too High

X

19.

Bat. Temperature too Low

X

20.

Bat. Temperature Sensor Fail

X

21.

Ambient temperature too high

22.

Ambient temperature too low

23.

Ambient temperature sensor fail

24.

Not used

25.

Output fuse blown

X

26.

Battery breaker open

X

27.

Digital input 3

28.

Digital input 4

29.

Digital input 5

30.

Digital input 6

Table 7: Overview Alarm settings