Alpha Technologies AlphaNet DSM Series DOCSIS User Manual

Page 38

Advertising
background image

38

745-814-B0-001, Rev. A

6.0

Data Management, continued
6.3

SCTE-HMS MIB Alarms, continued

6.3.1 SCTE-HMS Configurable Alarms, continued

Discrete Alarm Definitions and Common Settings

Discrete Alarms

Discrete Alarm

Value

Definition

Example

Settings

psInverterStatus

1

Inverter is off

Disable

psInverterStatus

2

AC Input line loss

EnableMinor

psInverterStatus

3

Inverter is in a local test cycle

Disable

psInverterStatus

4

Remote inverter test has been

initiated

Disable

psInverterStatus

5

The last Inverter test failed.

EnableMinor

psMajorAlarm

1

No alarm

Disable

psMajorAlarm

2

Service has been dropped or a

service interruption is imminent. This

is a general alarm; the cause of which

can be determined by looking in the

Discretes Table.

EnableMajor

psMinorAlarm

1

No alarm

Disable

psMinorAlarm

2

A non-service effecting condition has

occurred and should be monitored

EnableMinor

psTamper

1

Indicates status of enclosure door

tamper sensor: closed (door is open).

EnableMinor

psTamper

2

Indicates status of enclosure door

tamper sensor: open (door is closed).

Disable

psInputVoltagePresence

1

Digital value indicating that

line voltage is lost, based on

measurement of input voltage.

EnableMinor

psInputVoltagePresence

2

Indicates that line voltage is present

and within tolerance, based on

measurement of input voltage.

Disable

transponderInterfaceBusIdent

1

Remote device will respond to

commands from master transponder.

Disable

transponderInterfaceBusIdent

2

Local device is under local control and

will not respond to commands from

master transponder.

EnableMinor

transponderInterfaceBusIdent

3

Device is not responding.

EnableMajor

Table 6-5, Discrete Alarm Definitions and Common Settings