7 connecting the alarm and control connections – Alpha Technologies AlphaGen PN-6x-T 7.5kW 48Vdc User Manual

Page 63

Advertising
background image

042-288-B0-001, Rev. A2

63

4.0

The Engine Control Module, continued

4.7 Connecting the Alarm and Control Connections

Alarm output and communication connections are located on Terminal Block 1.

Fig. 4-4, Terminal Block 1

Terminal Block 1

Pin Alarm Signal Description Alarm Active State

1

Engine Run Common

Common

2

Engine Run

Closed with respect to Pin 1

3

Engine Run

Open with respect to Pin 1

4

Major Alarm Common

Common

5

Major Alarm

Closed with respect to Pin 4

6

Major Alarm

Open with respect to Pin 4

7

Minor Alarm Common

Common

8

Minor Alarm

Closed with respect to Pin 7

9

Minor Alarm

Open with respect to Pin 7

10 Not used

Not used

11

Not used

Not used

12 Not used

Not used

Pin 1

TB 1