Danger/poison, 4 battery installation – Alpha Technologies UPE-M Series User Manual

Page 24

Advertising
background image

24

031-145-C0-002 Rev. B

Battery Terminal Connections

The accompanying drawings are for illustrative purposes only. Various types of batteries with
different mounting styles and hardware may be shipped with the system. Always refer to the
battery manufacturers’ specifications for correct mounting hardware and torque requirements.
During maintenance procedures, refer to the manufacturers' specifications for the maintenance
torque requirements.

For AlphaCell batteries, use 65 inch-pounds upon installation, then re-torque to 50 inch-pounds.
Mounting hardware requirements may vary between battery manufacturers. Use only the hardware
recommended by your particular battery manufacturer.

Fig. 3-10, Battery Terminal Assembly

Battery Post

3/8" Spacer

Fuse

Flat Washer

Lock Washer

Nut

Battery Cable and

Crimp Connector to

Next Battery

3.0

Installation, continued

3.4

Battery Installation

Battery Identification

Each battery contains a date code usually located on a sticker near the center of the battery or
stamped in white ink near the POS terminal. This date code must be recorded in the battery’s
maintenance log. If batteries, other than those marketed by Alpha are used, consult the battery’s
manufacturers’ documentation for date code type and placement.

MMYY

CALIF. PROPOSITION 65
WARNING
Battery posts, terminals
and related accessories
contain lead and lead
compounds, chemicals
known to the state of Calif.
to cause cancer and
reproductive harm. Wash
hands after handling.

SHIELD EYES EXPLOSIVE GASES
CAN CAUSE BLINDNESS OR INJURY

NO SPARKS, FLAMES, OR SMOKING

SULFURIC ACID CAN CAUSE
BLINDNESS OR SEVERE BURNS

FLUSH EYES IMMEDIATELY WITH WATER
GET MEDICAL HELP FAST. KEEP OUT OF REACH OF CHILDREN

DANGER/POISON

Battery Date Code

located in this box

(0103 = Jan. 2003)