Continued, Installation, 4 utility power connection – Alpha Technologies UPE-8 User Manual

Page 27

Advertising
background image

2. Installation

27

031-165-C0-001 Rev. A

Coaxial Cable Connection

1. DO NOT remove SPI cover until all sources

of power have been removed. Verify SPI IS
NOT connected to power supply

2. Remove the two screws holding the cover

onto the SPI’s chassis.

3. Remove the SPI’s cover, exposing the

circuit board and seizure screw assembly.

Seizure

Screw

Assembly

2

3

1

Seizure Screw

Assembly

Side View

of

SPI Case

Circuit

Board

Stinger

Output Port

Coaxial Termination

4

5. Tighten the Seizure Screw to 35 Inch-

Pounds.

5

4. Insert the Coaxial Termination into the

Output Port on the bottom of the SPI.

6. Replace the SPI’s cover and reinstall the

screws.

7. Verify the switch on the top of the SPI is in

the ON position.

NOTE: To prevent arcing, and failure of the

unit, the center conductor (stinger) of
the coaxial termination must go fully
inside the seizure screw assembly.

ALT ON

7

6

6

2.4

Utility Power Connection,

continued