Danger/poison, Installation, 5 battery installation – Alpha Technologies BSM-3 Battery Side Module Enclosure User Manual

Page 18: Mmyy

Advertising
background image

1. Installation

18

033-082-C0-002 Rev. B

The accompanying drawings are for illustrative purposes only. Various types of

batteries with different mounting styles and hardware may be shipped with the

system. ALWAYS refer to the battery manufacturers’ specifications for correct

mounting hardware and torque requirements. During maintenance procedures, refer

to the manufacturers' specifications for the maintenance torque requirements.

For AlphaCell batteries, use 65 Inch-Pounds upon installation, then re-torque to 50

Inch-Pounds during maintenance.

Mounting hardware requirements may vary with battery manufacturers. Use only the

hardware recommended by your particular battery manufacturer.

1.5

Battery Installation

Battery Post

3/8" Spacer

Fuse

Flat Washer

Lock Washer

Nut

Battery Cable and

Crimp Connector to

Next Battery

1.4.1.

Date Code

1.4.2.

Battery Terminals

Each battery contains a DATE CODE usually located on a sticker near the center of
the battery or stamped in white ink near the POS terminal. This date code must be
recorded in the battery’s maintenance log. If batteries other than those installed by
Alpha are used, consult the battery’s manufacturers’ documentation for date code
type and placement.

MMYY

CALIF. PROPOSITION 65
WARNING
Battery posts, terminals
and related accessories
contain lead and lead
compounds, chemicals
known to the state of Calif.
to cause cancer and
reproductive harm. Wash
hands after handling.

SHIELD EYES EXPLOSIVE GASES

CAN CAUSE BLINDNESS OR INJURY

NO

SPARKS, FLAMES, OR SMOKING

SULFURIC ACID

CAN CAUSE

BLINDNESS OR SEVERE BURNS

FLUSH EYES IMMEDIATELY WITH WATER

GET MEDICAL HELP FAST. KEEP OUT OF REACH OF CHILDREN

DANGER/POISON

Battery Date Code

located in this box

(0103 = Jan. 2003)