Installation, A/b c/d, Continued – Alpha Technologies USM2.5 Status Monitor User Manual

Page 12: 3 battery monitor connections

Advertising
background image

018-041-C0-002 Rev. B

12

Connector

Pin #

String Reference

Wire Label

NetMentor Display (36V)

A/B

1

1A - (0Vdc)

A/B[C/D] NEG

2

1A + (+12Vdc)

Vbatt 1A [C] 12V

Battery #3 Vdc

3

2A + (+24Vdc)

Vbatt 2A [C] 24V

Battery #2 Vdc

4

3A + (+36Vdc)

Vbatt 3A [C] 36V

Battery #1 Vdc

5

1B + (+12Vdc)

Vbatt 1B [D] 12V

Battery #6 Vdc

6

2B + (+24Vdc)

Vbatt 2B [D] 24V

Battery #5 Vdc

7

3B + (+36Vdc)

Vbatt 3B [D] 36V

Battery #4 Vdc

8

1. Installation

1.3

Battery Monitor Connections

, continued

12V

24V

36V

12V

24V

36V

1

2

3

4

5

6

7

8

Battery String A

Battery String B

1A

2A

3A

1B

2B

3B

To Pow er Supply

A/B

C/D

1

2

3

4

5

6

7

8

Figure 1-7 Battery Monitor Connections for two 36Vdc battery packs

Not used in this configuration

Advertising