0 maintenance, 1 recommended maintenance tasks – Alpha Technologies AlphaCell SMU-HR User Manual

Page 15

Advertising
background image

15

745-680-B2-002, Rev. B

4.1 Recommended Maintenance Tasks

In order to prolong battery life, perform regular maintenance and inspections.

Monthly Maintenance

Keep the batteries and battery room clean.

Measure and record the ambient temperature of the battery-room.

Check for damage and overheating evidence on the terminal, container, and lid.

Measure and record the total voltage and floating current of the battery system.

Quarterly Maintenance

Measure and record the floating voltage of every on-line battery. If the voltage of

more than two cells is less than 13.0V after temperature adjustment, discharge the

battery and then recharge at the float rate. If the problem still exists, conduct yearly

or three-year maintenance procedures. If the problem persists, please contact Alpha

Technologies.

Yearly Maintenance

Check for loose connections.

Conduct a discharge test to check the exact load, discharging 30-40% of the

rated capacity.

Three-Year Maintenance

After three years of operation, conduct an 80% capacity test annually.

4.0 Maintenance