Alpha Technologies AlphaCell OPzS User Manual

Page 40

Advertising
background image

OPzS-BATTERY

40

14.0

Specifi cations, continued

Battery Water Quality Maximum Impurities (Parts per Million (PPM))

Requirements

Maximum Allowable Limits

Total Solids

350.0

Fixed Solids

200.0

Organic and Volatile

150.0

Iron

4.0

Chloride

25.0

Ammonium (NH4)

4.0

Nitrates (NO2)

10.0

Nitrates (NO3)

10.0

Manganese

0.07

Calcium and Magnesium

40.0

Table 14-9, Demineralized Water Impurities

«

List of Reference Standards

Stationary lead-acid batteries. General requirements and methods of test Part 1. Vented types.

EN60896-1, IEC 896-1

Sulphuric acid for use in lead-acid batteries

BS3031

Sulphuric acid and water for use in lead-acid batteries

DIN 43 530-1

Stationary lead-acid batteries accessories

DIN 40 740

Stationary lead-acid batteries - tubular positive plates

DIN 40 736

Safe operation of starter batteries

BS 6604

Safety reqs for secondary batteries and battery installations Part 2: Stationary lead-acid batteries

EN50 272-2 (VDE 0510)

Recommended Practice for Maintenance, Testing, and Replacement of Vented Lead-Acid
Batteries for Stationary Applications

IEEE 450

Recommended practice fro installation design and installation of vented lead-acid batteries for
stationary applications (ANSI/BCI)

IEEE 484

Sizing lead-acid batteries for stationary applications (BCI)

IEEE 485

Table 14-10, List of Reference Standards

«

Specifi cations and data are subject to change without notice.