Technical Specifications

The M4100 unit is the foundation of the M4000 Diagnostic Test System for Condition
Assessment of Power Apparatus
Note: A personal computer is required to operate the M4100

Power Specifications:

Output Voltage:

0 to 12 kV ac

Output Current:

100 ma continuous at 10 kV

200 ma > 30 minutes at 10 kV

300 ma > 4 minutes at 10 kV

Operating time period based on 50°c oper-
ating temperature. Longer durations at high
currents will be realized at lower operating
temperatures

Output Power:

3 kVa

Sinusoidal output signal internal generated
independent of input supply, No loss in per-
formance when used with portable generator

A.C. Input*:

95-264 V ac 47 to 63 Hz

16 a max at 110 V,

10 a max at 220 V

Measurement, Accuracy and
Range Test Frequency:

Test Frequency:

Range:

45 to 70 Hz independent
of input signa

l

Resolution:

0.1 Hz

Accuracy:

±1% of reading

Test Voltage:

Range:

25 V to 12 kV

Resolution:

1 V

Accuracy:

±1% of reading, ±1 V

Test Current:

Range:

0 to 5.0 a

Resolution:

0.1 μa

Accuracy:

±1% of reading, ±1 μa

Capacitance

:

Range:

0 to 100 μF

Resolution:

0.01 rF

Accuracy:

± 0.5% of reading, ± 1 rF

Inductance:

Range:

6 H to 10 MH

Resolution:

0.01 H

Accuracy:

± 0.5% of reading

Watts:

Range:

0 to 2 kW, actual

Resolution:

0.5 mW

Accuracy:

± 2% of reading at 10 kV,

± 0.03% of Va, ±0.5 mW

Dissipation Factor:

Range:

%PF

0 to ±100.00%

PF

0 to ±1.0000

% Tan d

0 to ±999.99%

Tan d

0 to ±9.9999

mW/Var

0 to ±9999.9

Resolution:

0.01% / 0.0001

Accuracy:

± 0.5% of reading

,

typical

±0.04% PF/Tan d
±0.0004 PF/Tan d

* There are power restrictions for input

voltages below 190 V AC.