Atec Agilent-6643A User Manual

Single-output 200 w gpib, Specifications

Advertising
background image

This series of 200 W linear-regulated
DC power supplies is designed to
maximize the throughput of DUTs
through the manufacturing test
process with fast up and down
programming time.

Valuable assemblies can be
destroyed by a minor component
failure that can allow a surge of
voltage or current to flow to the
DUT. Fast protection features,
including fast crowbar, mode
crossover protection, and the ability
to connect the protection circuitry
of multiple power supplies can
increase production yield.

Programming of the DC output and
the protection features can be done
either from the front panel or using
industry standard SCPI commands,
via the GPIB. Using the serial link,
up to 16 power supplies can be
connected through one GPIB
address. Test system integration
can be further simplified be using
the VXIPlug&Play drivers. The out-
put voltage and current can also be
controlled with analog signals. This
is helpful for certain types of noisy
environments, and also immediate
reactions to process changes.

Lab bench use is enhanced by the
fan speed control, which helps to
minimize the acoustic noise.

High Performance DC Power Supplies speed and accuracy for test optimization

Specifications

(at 0

˚

to 55

˚

C unless

otherwise specified)

More detailed specifications at www.agilent.com/find/6640

38

Fast, low-noise outputs

Analog control of output voltage and current

Fan-speed control to minimize acoustic noise

Parallel and series connections of multiple units

Built-in measurements and advanced programmable features

Protection features to ensure DUT safety

6641A - 6645A

Single-Output
200 W GPIB

6641A 6642A 6643A 6644A 6645A

Number of outputs

1

1

1

1

1

GPIB

Yes

Yes

Yes

Yes

Yes

Output ratings

Output voltage

0 to 8 V

0 to 20 V

0 to 35 V

0 to 60 V

0 to 120 V

Output current (40° C)

0 to 20 A

0 to 10 A

0 to 6 A

0 to 3.5 A

0 to 1.5 A

Maximum current (50° C/55° C)

18 A/17 A

9 A/8.5 A

5.4 A/5.1 A

3.2 A/3 A

1.4 A/1.3 A

Programming accuracy at 25°C ±5°C

Voltage

0.06% +

5 mV

10 mV

15 mV

26 mV

51 mV

Current

0.15% +

26 mA

13 mA

6.7 mA

4.1 mA

1.7 mA

Ripple and noise
from 20 Hz to 20 MHz

Voltage

rms

300 µV

300 µV

400 µV

500 µV

700 µV

peak-peak

3 mV

3 mV

4 mV

5 mV

7 mV

Current

rms

10 mA

5 mA

3 mA

1.5 mA

1 mA

Readback accuracy at 25°C ±5°C
(percent of reading plus fixed)

Voltage

0.07% +

6 mV

15 mV

25 mV

40 mV

80 mV

+Current

0.15% +

18 mA

9.1 mA

5 mA

3 mA

1.3 mA

-Current

0.35% +

40 mA

20 mA

12 mA

6.8 mA

2.9 mA

Load regulation

Voltage

1 mV

2 mV

3 mV

4 mV

5 mV

Current

1 mA

0.5 mA

0.25 mA

0.25 mA

0.25 mA

Line regualtion

Voltage

0.5 mV

0.5 mV

1 mV

1mV

2 mV

Current

1 mA

0.5 mA

0.25 mA

0.25 mA

0.25 mA

Transient response time Less than 100 µs for the output voltage to recover to its previous level (within 0.1% of
the voltage rating of the supply or 20 mV, whichever is greater) following any step change in load current of up to
50% of rated current

Supplemental Characteristics

(Non-warranted characteristics determined by design and
useful in applying the product)

Average resolution

Voltage

2 mV

5 mV

10 mV

15 mV

30 mV

Current

6 mA

3 mA

2 mA

1.2 mA

0.5 mA

OVP

13 mV

30 mV

54 mV

93 mV

190 mV

OVP accuracy

160 mV

400 mV

700 mV

1.2 V

2.4 V

Advertising