Atec Raytech-TR-Mark-III User Manual

Tr - ma r k iii, Three phase turns ratiometer, Tr-m

Advertising
background image

S

pecificationS

:

M

odel

:

tR-M

aRk

iii

S

ize

:

L: 470mm (18.5”) W: 371mm (14.6”) H: 190mm (7.5”)

W

eight

:

9.5 kg (21 lbs.)

i

nput

l

ine

p

oWeR

:

100 to 250 VAC 47-63 Hz, auto ranging, Fuse: 2A

t

eSt

V

oltage

:

User selectable 100, 40, 10, and 1Vac, 1A

p

anel

d

iSplay

:

Color LCD with back lighting and touch screen

f

Ront

p

anel

:

Sealed anodized

i

nteRface

:

9 pin RS232 serial / 2 USB 1.1 (1 host, 1 device)

M

eMoRy

S

toRage

:

Stores over 10,000 complete test results

R

atio

R

ange

:

0.8…16,000

o

peRating

t

eMpeRatuRe

-10° C to 60° C

S

toRage

t

eMpeRatuRe

-20° C to 70° C

f

eatuReS

:

• Automatic measurements of voltage, turns ratio, current, and phase displacement

• Easy one time hook up to the transformer

• Automatic test voltage range

• Displays deviation from a nominal ratio

• Simple touch screen operation

• Graphical tap changer display

• Tap changer interface

• Load on test object <0.05 VA

• Measures power transformers PTs and CTs

• Displays % error vs. name plate value

• Automatic phase vector detection

• Enhanced heavy-duty protection circuitry

• Emergency stop push button immediately turns off output

• Internal printer

• Data storage of over 10,000 measurements

• Data exchange with USB-key

• Mounted in rugged case for field-testing

• 5 Year standard warranty*

Range

Accuracy at 100 V or 40 V

Accuracy 10 V

Resolution

0.8 ... 2000

±0.06% Rdg ±1 LSD

±0.15 % Rdg ±2 LSD

5 Digits

2001 ... 4000

±0.1% Rdg ±1 LSD

±0.22% Rdg ±2 LSD

5 Digits

4001 ... 13000

±0.3% Rdg ±1 LSD

±0.5% Rdg ±2 LSD

5 Digits

13000 ... 16000

±0.4% Rdg ±1 LSD

not specified

5 Digits

c

able

S

et

/ a

cceSSoRieS

:

• H and X lead-set – 5m each

• H and X extensions – 10m each

• Safety ground, power cord

• External USB-key, USB and RS-232 Cable

• Instruction manual, printer paper (5 rolls)

• Cable bag

o

ptional

i

teMS

:

External trigger for tap changer testing

Three phase supply for phase shifting and Zig-Zag transformers

TR-Mark IIIR – 19” 4U Rackmount version available

Specifications are subject to improvement at any time.

Three Phase Turns Ratiometer

TR
-

Ma
R

k

iii

Raytech USA

90C Randall Avenue, Woodlyn, PA 19094

|

Ph: +610 833 3016

|

Toll Free: 888 484 3779

|

Fx: +610 833 3018

[email protected]

|

www.raytechusa.com

Current

Accuracy

Resolution

0 ... 1A

±0.001 A

0.1mA

Phase Angle

Accuracy

Resolution

±90 Degree ±0.05 Degree

0.01 Degree

Advertising