Atec Megger-MIG16-2 User Manual

Mig16-2, Megger impulse generator and hv test system

Advertising
background image

MIG16-2

Megger Impulse Generator and HV Test System

n

Rugged, portable field impulse generator

n

Two range 8/16 kV output

n

Powerful 1500 joules output

n

HV insulation testing to 20 kV

n

Proof/burn up to 20 kV, 115 mA

MIG16-2

Megger Impulse Generator and HV Test System

DESCRIPTION

The Megger impulse generator (thumper) MIG16-2 is
designed to provide quick, effective, accurate and safe fault
location, reducing system outages and customer minutes
lost.

The instrument comes in a rugged, yet portable,
enclosure. Its IP64 rating makes it suitable for use in even
environmentally hostile conditions.

The MIG16-2 offers the facility to undertake cable testing:
cable and fault diagnosis and pinpoint fault location using
acoustic methods.

FEATURES AND BENEFITS

High voltage module

n

Easy-to-use manual controls

n

Safety interlocks to prevent injury to operators

n

Safety interlocks to prevent any switching during high
voltage generation.

n

2-ranges ensure 100% of energy available at 8 & 16 kV

n

Powerful 1500 joules output assists rapid, accurate
pinpoint fault location even in difficult locations

n

High visibility HV status bar

n

External interlock

n

Detachable HV cable

n

Ergonomically designed transport handles and foot-step
allow for easy and comfortable transporation.

APPLICATIONS

HV testing (proof/insulation testing)

Used to prove the integrity of (and identify and confirm)
fault conditions in cable networks.

The variable output voltage can also be used for sheath
testing at 5 or 10 kV.

Proof/burn

Following a breakdown of the cable under test, a high
current is applied that stabilizes the fault condition. This
can assist pre-location and pinpointing of unstable faults.

Pinpoint fault location

Accurate pinpoint fault location is achieved using the
acoustic method, whereby the powerful 8/16 kV 1500-
joule surge generator (thumper) and an acoustic receiver
(Megger MPP2000) is used.

SPECIFICATIONS

Testing

Output: 0 - 20 kV (negative with regard to earth)
0 – 10 kV, 115 mA constant
0 – 20 kV, 58 mA constant
Resolution: 5 mA
Metering: Analog metering of current and voltage

Fault Conditioning

Proof/burn: 0 - 20 kV 58 mA
0 - 10 kV 115 mA

Advertising