The CMC 356 is the universal solution for testing all generations and types of protection relays.
Its powerful six current sources (three-phase mode: up to 64 A / 860 VA per channel) with a
great dynamic range, make the unit capable of testing even high-burden electromechanical
relays with very high power demands. Commissioning engineers will particularly appreciate
the possibility to perform wiring and plausibility checks of current transformers, by using
primary injection of high currents from the test set. The CMC 356 is the first choice for
applications requiring the highest versatility, amplitude and power. The CMC 356 can either
be operated by the Test Universe software running on a PC or by the front panel control device
CMControl.

Current generators
Setting range

6-phase AC (L-N)

6 x 0 ... 32 A

3-phase AC (L-N)

3 x 0 ... 64 A (Group A II B)

1-phase AC (LL-LN)

1 x 0 ... 128 A (Group A II B)

DC (LL-LN)

1 x 0 ... ±180 A (Group A II B)

Power

2

6-phase AC (L-N)

6 x 430 VA typ. at 25 A
6 x 250 W guar. at 20 A

3-phase AC (L-N)

3 x 860 VA typ. at 50 A
3 x 500 W guar. at 40 A

1-phase AC (LL-LN)

1 x 1000 VA typ. at 80 A
1 x 700 W guar. at 80 A

1-phase AC (L-L)

1 x 1740 VA typ. at 50 A
1 x 1100 W guar. at 40 A

1-phase AC (L-L-L-L)

1 x 1740 VA typ. at 25 A
1 x 1100 W guar. at 20 A

DC (LL-LN)

1 x 1400 W typ. at ±80 A
1 x 1000 W guar. at ±80 A

1000

800
600
400
200

0

0

10

20

30

40

50

60

Output current / A

3-phase AC (L-N)

6-phase AC (L-N)

Output po

w

er (typ.) / V

A

1-phase AC (L-L-L-L)

1-phase AC (L-L)

1-phase AC (LL-LN)

0

100

120

2000
1600
1200

800
400

0

20

40

60

80

Output current / A

Output po

w

er (typ.) / V

A

Accuracy

3

error < 0.05 % rd.

4

+ 0.02 % rg.

4

typ.

error < 0.15 % rd. + 0.05 % rg. guar.

Distortion (THD+N)

5

< 0.05 % typ., < 0.15 % guar.

Resolution

1 mA

Max. compliance voltage
(L-N)/(L-L)/(L-L-L-L)

35 Vpk / 70 Vpk / 140 Vpk

Connection banana sockets

4 mm (0.16 in) banana sockets
(32 A continuously)

Connection combination socket

Group A only (25 A continuously max.)

Voltage generators
Setting range

4-phase AC (L-N)

4 x 0 ... 300 V (VL4(t) automatically
calculated: VL4 = (VL1+VL2+VL3)*c
or freely programmable)

3-phase AC (L-N)

3 x 0 ... 300 V

1-phase AC (L-L)

1 x 0 ... 600 V

DC (L-N)

4 x 0 ... ±300 V

Power

3-phase AC (L-N)

3 x 100 VA typ. at 100 ... 300 V
3 x 85 VA guar. at 85 ... 300 V

4-phase AC (L-N)

4 x 75 VA typ. at 100 ... 300 V
4 x 50 VA guar. at 85 ... 300 V

1-phase AC (L-N)

1 x 200 VA typ. at 100 ... 300 V
1 x 150 VA guar. at 75 ... 300 V

1-phase AC (L-L)

1 x 275 VA typ. at 200 ... 600 V
1 x 250 VA guar. at 200 ... 600 V

DC (L-N)

1 x 420 W typ. at ±300 V
1 x 360 W guar. at ±300 V

Output voltage / V

Output po

w

er (typ.) / V

A

1-phase AC (L-L)

1-phase AC (L-N)

3-phase AC (L-N)

4-phase AC (L-N)

300

250

200

150

100

50

0

0

100

200

300

400

500

600

Accuracy

error < 0.03 % rd.

4

+ 0.01 % rg.

4

typ.

at 0 ... 300 V
error < 0.08 % rd. + 0.02 % rg. guar.
at 0 ... 300 V

Distortion (THD+N)

5

0.015 % typ., < 0.05 % guar.

Ranges

150 V / 300 V

Resolution

5 mV / 10 mV in range 150 V / 300 V

Connection

4 mm (0.16 in) banana sockets /
combination socket (1,2,3,N)

Generators, general
Frequency

range sine signals

6

10 ... 1000 Hz

range harmonics /
interharmonics

voltage: 10 ... 3000 Hz

7

current: 10 ... 1000 Hz

range transient signals DC ... 3.1 kHz

7

accuracy / drift

±0.5 ppm / ±1 ppm

resolution

< 5 µHz

Phase

angle range

-360° ... +360°

resolution

0.001°

error at 50 / 60 Hz

voltage: 0.02° typ., < 0.1° guar.
current: 0.05° typ., < 0.2° guar.

3

Bandwidth (-3 dB)

3.1 kHz

Technical Data

1

1

All data specified are guaranteed, except where indicated otherwise.

OMICRON guarantees the specified data for one year after factory calibration,

within 23 °C ±5 °C (73 °F ±10 °F) in the frequency range from 10 to 100 Hz and

after a warm-up phase > 25 minutes

2

Typical AC values valid for inductive loads (e.g. e/m relays)

3

Rload: 0 ... 0.5 W

4

rd. = reading, rg. = range

5

THD+N: Values at 50/60 Hz, > 1 A / 20 V with 20 kHz bandwidth

6

For current outputs amplitude derating at > 380 Hz

7

Amplitude derating at > 1000 Hz