Atec Megger-TXL Series User Manual

Discharging process controlled by a torkel unit, Connect directly to the battery under test

Advertising
background image

TXL830, TXL850 and TXL870

Extra load units for TORKEL test system

TXL830, TXL850 and TXL780

Extra load units for TORKEL test system







DESCRIPTION

TXL

These resistive extra loads do not perform any regulating

functions.

They are designed for use together with TORKEL battery load
units. Their purpose is to provide higher load currents for use in

constant current or constant power tests. Together, TORKEL and
the TXL extra loads form a system that can discharge batteries
with currents of up to several kA. TXL extra loads are connected
directly to the battery, and TORKEL measures the total current

using a clamp-on ammeter.

TXL extra loads are shut down automatically when TORKEL is
stopped.


TORKEL / TXL - systems examples

Max. constant current
(A)

Number of
TORKEL-units

Number of
TXL-units

TORKEL 820 + TXL830, 12 V battery (6 cells)

1)

234 1

1

571 1

4

918 1

6

TORKEL 820 + TXL830, 24 V battery (12 cells)

1)

495 1

1

1170 1

4

1890 2

6

TORKEL 820 + TXL850, 48 V battery (24 cells)

1)

499 1

1

1189 1

4

1918 2

6

1)

Discharge from 2.15 V to 1.8 V per cell



Max. constant current
(A)

Number of
TORKEL-units

Number of
TXL-units

TORKEL 840/860 + TXL830, 24 V battery (12 cells)

1)

263 1

1

670 2

2

1005 3

3

TORKEL 840/860 + TXL850, 48 V battery (24 cells)

1)

264 1

1

909 2

3

TORKEL 840/860 + TXL870, 110 V battery (54 cells)

1)

188 1

1

532 2

4

845 2

8

TORKEL 840/860 + TXL870, 120 V battery (60 cells)

2)

194 1

1

557 2

4

895 2

8

TORKEL 840/860 + TXL870, 220 V battery (108 cells)

1)

94 1

1

266 2

4

423 2

8

1)

Discharge from 2.15 V to 1.8 V per cell

2)

Discharge from 2.15 to 1.75 V per cell








„

Provide higher load currents for

concurrent power tests

„

Discharging process controlled by a

TORKEL unit

„

Connect directly to the battery under

test

Advertising