Lightweight and ruggedly constructed for

years of field or lab use

Economical liquid dielectric testing solution

Simple set-up

Semi-automatic operation

CIRCUIT

BREAKER

SAFETY and DESIGN FEATURES

ENVIRONMENTAL

CONDITIONS

TESTING AppLICATIONS

DESCRIpTION

Specifications are subject to change without notice.

Brochure No. 10104

Center tapped high voltage transformer.

Safety interlock engaged when lid is open.

Fast acting relay ensures immediate cutout at flashover.

Lamp indicating AC power on.

Lamp indicating test sample breakdown.

Fuses are located on the input to the test set and on the primary of

the high voltage transformer.

Zero start interlock

Memory voltmeter retains breakdown voltage.

The test compartment is provided with outlet for convenient plug-in

of motor driven stirrer when testing to ASTM D1816 and VDE standards.

Measure the breakdown voltage of
insulation fluids used in transformers,
capacitors, bushings and related high
voltage equipment. With the appropriate
oil vessel test cell, these test sets are
designed to perform tests in accordance
with standards ASTM D1816, ASTM
D877, IEC 60156, BS 148, VDE 0370, plus
other applicable standards.

Three standard models rated at 60, 75,
and 100 kV are available. The operating
controls are conveniently grouped on
the front panel and include a large,
easy-to-read digital voltmeter, on/off
switch with indicator light, rate of rise
selector switch, plus a start/reset switch.
The test compartment is provided with
a transparent cover interlocked to the
test circuit with a limit switch to ensure
full operating safety.

The test set is semi-automatic. The liquid
to be tested is placed in the test cell and
then placed in the test compartment
on the cradle contacts, the rate of rise
is selected, the test chamber lid closed,
and the switch moved to start position.
The test set will automatically raise the
voltage. When a breakdown of the liquid
occurs, the test sample failure lamp
will illuminate, and the meter will hold
the breakdown voltage level.

Model LD60

Model LD75

Liquid Dielectric Test Sets

10-40°C, indoor/outdoor in fair

weather

Humidity <95% non-condensing

Altitude <3000 ft (1000 meters)