7 Fluke Corporation Fluke 430 Series II Three-Phase Energy and Power Quality Analyzers

Environmental

Operating temperature

0 °C ~ +40 °C; +40 °C ~ +50 °C excl. battery

Storage temperature

-20 °C ~ +60 °C

Humidity

+10 °C ~ +30 °C: 95 % RH non-condensing
+30 °C ~ +40 °C: 75 % RH non-condensing
+40 °C ~ +50 °C: 45 % RH non-condensing

Maximum operating altitude

Up to 2,000 m (6666 ft) for CAT IV 600 V, CAT III 1000 V
Up to 3,000 m (10,000 ft) for CAT III 600 V, CAT II 1000 V
Maximum storage altitude 12 km (40,000 ft)

Electro-Magnetic-Compatibility

(EMC)

EN 61326 (2005-12) for emission and immunity

Interfaces

mini-USB-B, Isolated USB port for PC connectivity

SD card slot accessible behind instrument battery

Warranty

Three years (parts and labor) on main instrument, one year on accessories

Included accessories

Power options

BC430 Power Adapter

International plug adapter set

BP290 (Single capacity Li-ion battery) 28Wh (7 hours or more)

Leads

TL430 Test lead and Alligator clip set

Color coding

WC100 color coding clips and regional decals

Flexible current probes

i430flex-TF, 24 inch (61cm) length, 4 clamps

Memory, Software and

PC connection

8 GB SD card

PowerLog on CD (includes operator manuals in PDF format)

USB cable A-Bmini

Carrying case

C1740 Soft Case for 434-II and 435-II

C437 Hard Case with rollers for 437-II

* ± 5 % if ≥ 1 % of nominal voltage ± 0.05 % of nominal voltage if < 1% of nominal voltage

** 50Hz/60Hz nominal frequency according to IEC 61000-4-30

*** 400Hz measurements are not supported for Flicker, Mains Signaling and Monitor Mode.

**** for nominal voltage 50 V to 500 V

Wiring configurations

1Ø + NEUTRAL

Single phase with neutral

1Ø SPLIT PHASE

Split phase

1Ø IT NO NEUTRAL

Single phase system with two phase voltages without neutral

3Ø WYE

Three phase four wire system WYE

3Ø DELTA

Three phase three wire system Delta

3Ø IT

Three phase system without neutral WYE

3Ø HIGH LEG

Four wire three phase Delta system with center tapped high leg

3Ø OPEN LEG

Open delta three wire system with 2 transformer windings

2-ELEMENT

Three phase three wire system without current sensor on phase L2/B (2 watt meter method)

2½-ELEMENT

Three phase four wire system without voltage sensor on phase L2/B

INVERTER EFFICIENCY

dc voltage and current input with ac output power (automatically displayed and selected in Inverter Efficiency mode)

General specifications

Case

Design Rugged, shock proof with integrated protective holster

Drip and dust proof IP51 according to IEC60529 when used in tilt stand position

Shock and vibration Shock 30 g, vibration: 3 g sinusoid, random 0.03 g

2

/Hz according to MIL-PRF-28800F Class 2

Display

Brightness: 200 cd/m

2

typ. using power adapter, 90 cd/m

2

typical using battery power

Size: 127 mm x 88 mm (153 mm/6.0 in diagonal) LCD

Resolution: 320 x 240 pixels

Contrast and brightness: user-adjustable, temperature compensated

Memory

8GB SD card (SDHC compliant, FAT32 formatted) standard, upto 32GB optionally

Screen save and multiple data memories for storing data including recordings (dependent on memory size)

Real-time clock

Time and date stamp for Trend mode, Transient display, System Monitor and event capture