Atec Magna-Power-NH300 User Manual

Harmonic neutralizer, Why neutralize harmonics, Models and ratings ac harmonic waveforms

Advertising
background image

www.magna-power.com

29

Harmonic Neutralizer

Magna-Power Electronics Harmonic Neutralizers eliminate
families of harmonic components by multiplying the number
of input phases with specially wound magnetic components.
These transformers, in combination with equally loaded,
high-power DC power supplies, off er a cost-eff ective solution
to maintaining power quality at acceptable levels. Harmonic
Neutralizers are packaged in cabinetry designed to be inte-
grated with multiple MT Series VI installations.

Why Neutralize Harmonics?

Input current harmonics are a by-product of nearly all

power supplies. Power can only be delivered to the load if the

frequency and phase of the voltage and current match. For a

three phase power supply using a three phase input recti-

fi er, the input current has a theoretical spectrum of 6n±1

where n is an integer incrementing from 1; this is known as

a 6-pulse waveform. This means that a power supply with

a three phase input rectifi er will produce input currents at

1, 5, 7, 11, 13, 17, 19 ... times the fundamental frequency.

The theoretical magnitude decays as the reciprocal of the

harmonic component. The 5th and 7th harmonic compo-

nents have magnitudes of 20% and 14% of the fundamental

component, respectively.
Harmonics currents in power systems can fi nd unusual

paths and can cause problems if the magnitude is signifi cant

and there are loads sensitive to harmonic frequencies. For

example, lighting ballasts have series connected capacitors

and inductors which can be excited by harmonic currents.

IEEE has introduced standard, IEEE 519, which defi nes

recommended limits. Implementing this standard requires

a knowledge of the power system and other loads producing

harmonics. Unfortunately, the standard can allow the same

power supply to possibly exceed limits in one application

and not in another. In the same respect, a power supply may

or may not can cause a harmonic related problem with or

without meeting IEEE 519. The best solution to minimize

the risk of a harmonic problem is to eliminate the harmonic

current at the source.

Models and Ratings

AC Harmonic Waveforms

The following fi gures are representative of expected AC

current waveforms for the various pulses available from

Magna-Power Electronics power supplies. As standard, mod-

els 2 kW through 150 kW produce 6-pulse waveforms, while

250 kW models produce 12-pulse waveforms. Magna-Power

Electronics Harmonic Neutralizers suppress families of

harmonics by increasing the number of power phases. It can

be used when multiple power supplies are used in series or

parallel and are equally loaded. Harmonic Neutralizers can

produce 12-pulse, 18-pulse, 24-pulse, or 48-pulse waveforms

which have harmonic current components on the order of

12n±1, 18n±1, 24n±1, or 48n±1, respectively. The following

fi gures show the theoretical difference for waveforms with a

different number of pulses. Harmonic Neutralizers are pro-

tected with appropriate sized primary-side circuit breakers.

Size Diagrams

0

0.005

0.01

0.015

0.02

0.025

0.03

−1

−0.8

−0.6

−0.4

−0.2

0

0.2

0.4

0.6

0.8

1

Time (s)

6-Pulse Waveform

0

0.005

0.01

0.015

0.02

0.025

0.03

−1

−0.8

−0.6

−0.4

−0.2

0

0.2

0.4

0.6

0.8

1

Time (s)

12-Pulse Waveform

0

0.005

0.01

0.015

0.02

0.025

0.03

−1

−0.8

−0.6

−0.4

−0.2

0

0.2

0.4

0.6

0.8

1

Time (s)

18-Pulse Waveform

0

0.005

0.01

0.015

0.02

0.025

0.03

−1

−0.8

−0.6

−0.4

−0.2

0

0.2

0.4

0.6

0.8

1

Time (s)

24-Pulse Waveform

Model

Power
Modules

Power
(kW)

Pulse
No.

Weight
(lbs)

Size
(H” x W” x D”)

HN200-12

2 x 100 kW

200

12

935

62.5 x 24 x 31.5

HN300-12

2 x 150 kW

300

12

1602

62.5 x 24 x 31.5

HN400-12

4 x 100 kW

400

12

1670

62.5 x 24 x 31.5

HN450-18

3 x 150 kW

450

18

1982

62.5 x 24 x 31.5

HN500-24

2 x 250 kW

500

24

3003

62.5 x 24 x 31.5

HN600-12

4 x 150 kW

600

12

3003

62.5 x 24 x 31.5

HN1000-48 4 x 250 kW

1000

48

9012

62.5 x 72 x 31.5

4.250

62.500

24.000

1

2

3

4

1

2

3

Air Exhaust Fans

Input Circuit Breakers
(Some Models Have
One Circuit Breaker)

Air Intake

4

AC Input Entry

Advertising