Atec Rx-Cx-Monitor User Manual

Atec Equipment

Advertising
background image

Specifi cations are subject to change without notice.

©2013 Rx Monitoring Services Inc.

The

Cx Monitor® is a power quality monitor adapted

specifi cally for the needs of a commissioning agent.

The monitor gathers all of the voltage and current

data required for all of the commissioning tests as well as

provides a means for gathering wireless T&H or DC voltage

data for over one hundred (100) locations! The

Cx Monitor®

is equipped to simultaneously monitor in real time, voltage on

ten (10) separate channels and current on fi ve (5) separate

channels. This is ideal for documenting the testing of genera-

tors, UPS’s and transfer switches.

General Specifi cations:

• Clock: Leap Year, 24-Hour, with time zone info

• Real-time Clock Accuracy: +/- 1 sec / day max.

• Internal Memory: Minimum 512Mbytes high speed

NAND Flash

• Wireless 802.11g Integration (Ad-hoc mode)

• 10/100Mbit Ethernet; FTP, SMTP, HTT P, HTT PS, SSL, SSH.

• USB Mass storage class support

• Remote access though secure remote Ethernet tunneling

• Max number of events: Only limited by internal memory

• Power Requirements: 100V-240V ACrms +/-10% 47-63 Hz

10Watt s 24Vdc 0.5Arms Center Barrel positive

• UPS standby time: Programmable Max time 10 Minute

• Dimensions: 11.5 x 10.25 x 4 Inches.

(Height x Width x Depth)

• Weight: 5.55lb

Voltage and Current Measurement:

Low Frequency

• Voltage Measurement Range: 0-600Vrms

• Voltage input impedance: 1.2Mohm

High Frequency

• Voltage Measurement Range: 0-2,500V

• Measurement type: AC coupled digital threshold trigger

500 sample buff er per channel

• Voltage input impedance: 1.2Mohm

Current Measurement Range (Probe dependant)

• Current input type: AC/DC +/- 6Vdc Input impedance

120K, 1M to gnd.

Environmental & Safety

• Operating environment: Indoors

• Storage Temperature: -20ºC to 50ºC

(-4F-122F)

• Operating Temperature: 0ºC to 40ºC

(32F-104F)

• Max Changes per hour temp: 30ºC

• Operating Humidity: 80% Max

Non-Condensing

• Conforms to IEC61010 CAT III 600V

Synchronization & Sampling:

Low Frequency:

• Sampling Frequency: 256 samples/cycle

• A/D Resolution: 16 bit oversampled

voltage 2X ; current 4X

• Auto 50/60 Hz ; or locked to input

• Voltage & Current RMS triggers ; Cross

triggering

• Adaptable trigger thresholds

High Frequency:

• 1.666Msample/sec per channel.

• A/D Resolution: 12 bit

Advertising