62.5 to >625 kVA
47 to 500 Hz

UMS Option

The battery support system for a single cabinet UMS
installation (62.5 kVA, 50 kW) consists of 30 sealed,
maintenance free, immobilized electrolyte batteries installed
in a Zone 4 cabinet. The UMS system DC
voltage regulator provides for automatic charging of the
battery system to maintain the proper float voltage.

A battery disconnect is located in the center of the
battery cabinet front door.

Battery support time at full load (50 kW) is approximately
15 minutes. The waveform quality at the end of the battery
support time meets the requirements of MIL-STD 1399,
section 300A, Types I, II and III power forms.

On-Line, No-Risk Battery Test

High Performance AC Power
for Today’s Electronic Loads

Pacific’s unique master/slave configuration
allows up to ten 62.5 kVA mainframes to be
paralleled in the field. Any mainframe may be
designated as the master. A failed unit is
automatically disconnected from the power
grid providing unmatched mission reliability.

Pacific’s MS Series Power
Source Systems Feature:

• Maximum system reliability.

• Lower installation cost.

• Lower maintenance cost.

• Unmatched performance/price ratio.

• Rugged, powerful output.

• All frequency operation.

• Facility/test power flexibility.

• Simple display and diagnostics.

• Uninterruptible Power Source configuration

(UMS Option) readily available.

MS Series Battery
Support Systems

For Application Engineering Assistance

Contact the factory directly

Consult your local PPS Representative

© 2008 Pacific Power Source, Inc.

Subject to change without notice.

#8MSCAT0908

17692 Fitch, Irvine, CA 92614 USA

Call direct: +1 949-251-1800 • Fax: +1 949-756-0756

US: 800-854-2433

E-mail: [email protected] • www.pacificpower.com

MS Series

Solid State Frequency Converter

www.pacificpower.com

T h e P o w e r o f E x p e r t i s e

This feature of the UMS system provides the ability to
perform a battery test on command from the front panel
or RS-232 serial port. Test results are displayed on the
front panel and are available over the serial port as a
part of the system diagnostics. A battery failure during
the test will not cause the system to drop the load or
distort the output waveform.

As a privately held, leading manufacturer of high-quality AC Power Conversion
Equipment, Pacific Power Source, Inc. offers standard catalog products that
range in power from 500 VA to >625 kVA. Low-power products include line
conditioners, frequency converters and Programmable AC Power Sources.
High-power systems include programmable power test equipment, power line
conditioners, frequency converters and uninterruptible AC Power Sources.

The Leader in Power Technology

Founded in 1971, the Irvine, California, company was an early pioneer
in the development of linear solid-state power conversion for use in
high-reliability applications. The company now manufactures both
advanced linear and broadband switching types of AC Power Sources.

High Power
Programmable AC Test
System/Utility Line
Disturbance Simulator

Add Pacific’s M3235 SCU-UPC32 Programmable Controller option and convert
your 3060-MS into a fully featured AC Power Test System. When controlled by the
SCU-UPC32 Programmable Controller, the AC Power Source will offer almost any
combination of waveform, voltage, and/or frequency variation experienced on the
local AC Mains.

Pacific Power Source has long been the leader in programmable AC Power
Sources. Using a combination of software and hardware features, the operator
may generate line harmonics, frequency shifts, voltage transients and other
power line disturbances for application to the equipment under test.

The UPC controller is essentially a 3Ø AC arbitrary waveform generator and
precision AC metering system. The waveform for each phase may be indepen-
dently selected and may be independently varied in amplitude and phase angle
with respect to phase A.

The UPC output metering samples the output volts and amps at 512 samples per
measurement using a 12-bit A/D converter. This technique provides exceptional

metering accuracy and resolution (20 bits), and delivers a high-

fidelity waveform back to a host computer for analysis.

The UPC includes a remote GPIB interface compatible with

IEEE-488.2 and SCPI. An available option is an RS-232 serial port

that operates up

to 38.4 kBaud.