Atec T-R-100ADM Mk4 User Manual

100adm, Current injection system

Advertising
background image

100ADM

Current Injection System

Features

 Clear and simple user interface
 0-100A output current
 Current limit mode for fine current

control

 True RMS metering with single

cycle capture memory ammeter

 Multi-function auto-ranging timing

system

 Auxiliary DC and AC output
 Large back-lit liquid crystal display
 Thermal and over-current protection
 Compact and portable
 Automatic mains voltage selection
 Shoulder carry strap

The 100ADM mk4 provides commissioning and maintenance
engineers with a flexible system for testing protective systems. It
has an easy to understand panel layout and a simple user interface.
The status of every function can be seen at a glance, and there are
no complex menus to navigate.

The 100ADM mk4 keeps the familiar user interface of previous
models but adds a new metering system that accurately measures
the RMS of a single cycle. It also features a new current limit mode
to provide very fine control of low currents, even into low impedance
loads. Current limit mode also assists in testing self-powered
overcurrent protection as fitted to many 11kV ring main units.

The unit has a range of outputs allowing injection of currents as low
as a few mA and as high as 100A. Voltages up to 240V are
available allowing high impedance current relays and voltage relays
to be tested. Four true RMS metering ranges are provided, and the
full scale of the meter (and trip level) can be set independently of
output tap. Industry standard safety connectors are used on all
inputs and outputs for convenience, reliability and safety.

A very flexible two channel timing system is provided, allowing trip
times, reset times and reclose times to be quickly measured to a
high degree of accuracy. The timer auto-ranges to measure from
1ms to 99999.9s.

The back-lit display on the 100ADM mk4 is bright and

clear with a wide viewing angle. The results of a test can

be seen here as they appear on the display.

The outputs of the 100ADM mk4 are well protected. The main
output is protected by overcurrent, duty cycle and thermal trips. The
auxiliary dc supply is protected by a current limit, and the auxiliary
AC supply is fuse protected.

mk4

7

IEEE no. Type

27/59

Under/over voltage

37

Undercurrent

50/76

Instantaneous overcurrent

Ground fault relay

51

IDMT overcurrent relay

59G

Neutral voltage displacement

67

Directional overcurrent (basic
tests)

IEEE no. Type

79

Auto recloser

86

Lockout relay

94

Tripping relay

90V

Voltage regulating relay

Miniature circuit breakers
Circuit breakers for
equipment

Thermal relays

100ADM mk4 Applications

The unit is supplied
with a comprehensive
lead set in a sturdy
carrying
case.

A 24-220VDC switch-mode stabilised DC supply with current limiting
is provided to power the relay under test. An isolated, separately
switched 110VAC auxiliary supply is also provided.