The Flood Sensor with attached sensor cable is activated by liquid (i.e. water, fluid, etc.) making contact with an

attached Flood Sensor Cable of any length. The Flood Sensor Cable can detect as little water as a single drop when

it makes contact with AVTECH Software’s patented Flood Sensor Cable. If the Flood Sensor is installed properly,

this will result in an alert condition where the Room Alert hardware, Device ManageR software and/or other

monitoring application will send out alerts and/or take an automatic corrective action.

Components

The Flood Sensor with Flood Sensor Cable

includes the following components: (1) Flood

Sensor device, (1) Flood Sensor Cable, (1) 25´

RJ-11 Leader cable with special connector, (1)

5V Power Adapter for use with 110-240 VAC,

(1) 25´ Sensor Cable (24 gauge speaker cable)

and (2) mounting screws.

Setup And Adjustments

The Flood Sensor is designed to be wall mounted above any anticipated water line and near a 110-240 VAC power

source where the 5V power adapter can be connected. Mount the Flood Sensor to a vertical surface like a wall or

pillar using the two mounting screws that are included. Then, locate the Flood Sensor Cable where you are most

concerned about water or flooding. Naturally, you’ll want this to be where water is most likely to run or settle.

CAUTION: The Flood Sensor Cable is designed to be located where water or flooding is most likely to occur. The actual Flood

Sensor device is NOT designed to come into contact with water. Mount the Flood Sensor (i.e. the black box) to a vertical surface

like a wall or pillar using the included mounting screws. Because the Flood Sensor uses main power via the AVTECH Software

5V Power Adapter, it is NOT appropriate to allow the Flood Sensor device to be located where it may be submerged underwater

or come into contact with water for any length of time. For this reason, there is a 25’ RJ-11 Leader cable that connects the Flood

Sensor Cable to the Flood Sensor device.

The Flood Sensor Cable is designed to be located where water or flooding is most likely to occur. Typically,

users will locate the Flood Sensor Cable along the floor next to a wall or circling valuable IT equipment. Some

applications may require a creative approach. For example, if monitoring for leakage in a drop ceiling, you

might run the Flood Sensor Cable along a plastic trough or inside a collection tray positioned to collect dripping

water (i.e. like from an air conditioner). If water runs along pipes, you could coil the Flood Sensor Cable around

the pipe so that water has to touch it as it runs down the pipe.

Once the Flood Sensor and Flood Sensor Cable are mounted and located as desired, connect these together

using the 25´ RJ-11 Leader cable. The RJ-11 connection plugs into the Flood Sensor (i.e. the black box) while

the special connector plugs into the mating connector on the Flood Sensor Cable. These arrive connected by

default although are often disconnected during the installation process for easy installation.

Flood Sensor with Flood Cable

Instructions For Installing The Flood Sensor with Flood Cable

AVTECH Software

Phone 401.628.1600

Sales 888.220.6700

Web AVTECH.com

Application Note

Room Alert

Advertising
This manual is related to the following products: