EXTERNAL LOAD CALCULATIONS FOR DIRECT BURIED CONDUIT

25701 Science Park Drive

Cleveland, Ohio 44122

216-464-3400

1-800-3CARLON (322-7566)

www.carlon.com

EXTERNAL LOADS ON DIRECT BURIED PVC OR HDPE CONDUIT OR DUCT

FALL INTO TWO CATEGORIES, DEAD LOADS (EARTH LOADS) AND LIVE

LOADS. DEAD LOADS ARE BASED ON THE WEIGHT OF THE COLUMN OF

SOIL ABOVE THE BURIED CONDUIT OR DUCT. LIVE LOADS ARE FROM

DIFFERENT SOURCES SUCH AS HIGHWAYS, AIRPORT RUNWAYS OR

RAILWAYS. LIVE LOADS HAVE LITTLE EFFECT ON CONDUIT

PERFORMANCE EXCEPT AT SHALLOW DEPTHS (4’ OR LESS FOR

HIGHWAY LOADS).

THE TOTAL LOAD IS THE SUMMATION OF THE DEAD LOADS AND OF THE

LIVE LOADS. THE TOTAL LOAD SHALL BE LESS THAN THE LOAD

(MAXIMUM LOAD) REQUIRED TO CHANGE THE INSIDE DIAMETER OF THE

CONDUIT OR DUCT BY ARBITRARY DATUM OF 5% DEFLECTION. THIS

DEFLECTION, CAUSED BY THE TOTAL LOAD, IS FAR BELOW THAT WHICH

WOULD CAUSE DAMAGE TO THE PVC WALL OF THE CONDUIT OR DUCT.

THE MAXIMUM LOAD (W) CAN BE CALCULATED WITH THE FOLLOWING

FORMULA:

W = [

X *(0.149*PS + 0.061*E

1

)]/[D*K]

W = MAXIMUM LOAD (lb/in

2

)

X = DEFLECTION (%/100)

PS = PIPE STIFFNESS (lb/in

2

)

E_ = BEDDING SOIL MODULUS (lb/in

2

)

D = DEFLECTION LAG FACTOR

K = BEDDING CONSTANT