C.E. Niehoff & Co. A2-213/A2-214 Regulator Installation User Manual

Installation instructions

Advertising
background image

II0103B

Page 1 of 1

A2-213 and A2-214

Regulators

C. E. Niehoff & Co. • 2021 Lee Street • Evanston, IL 60202 Tech Services Hotline 800-643-4633

Table 1 – Voltage Select Switch Position

4 Voltage Setpoints (Fig. 1)

Position 1

27.5 V

Position 2

28.0 V

Position 3

28.5 V

Position 4

29.0 V

Battery Type

Maintenance (D Category)

Maintenance-Free (Group 31)

Maintenance-Free (Group 31)

Battery Isolator setpoint

Note: On Group 31 batteries, if boiling or excessive gassing occurs with high voltage
setpoint (position 3), change to medium voltage setpoint (position 2).

Figure 1 – 4 Voltage Setpoints

1. Before installing, turn regulator over and select

appropriate voltage setpoint for battery type
(See Table 1 and Fig. 1).

2. Install new regulator as described below:

a. Mount new regulator on alternator in the same

position as the previous regulator.

b. Use screws and washers (if supplied),

2 or 4 depending on number of original

mounting holes in alternator. Torque regulator

mounting screws to 8.5 Nm/75 lb. in.

3. Plug the alternator-to-regulator harness into the

regulator.

4. A2-214 regulator connections:

• Connect IGN terminal to ignition source

through existing switch. Torque M5 terminal

nut on regulator to 4.5 Nm/40 lb. in.

• D+ terminal provides 28 VDC sense voltage

to multiplex controller. When connecting D+

terminal to controller through a relay, the

relay coil must be diode protected and rated

for proper voltage. Torque M6 terminal nut

on regulator to 4.5 Nm/40 lb. in.

• Connect P terminal to tachometer or relay.

P terminal taps AC voltage, typically half

the charge voltage. Torque M6 terminal nut

on regulator to 4.5 Nm/40 lb. in.

NOTE: If you are replacing an A2-211 regula-

tor with an A2-214 regulator, the existing R

terminal lead should now be connected to

the P terminal on the new A2-214 regulator.

See step above for details.

Installation Instructions

1

2 3

4

5. A2-213 regulator connections:

• Connect IGN terminal to ignition source

through existing switch. Torque M5 terminal

nut on regulator to 4.5 Nm/40 lb. in.

• D+ terminal provides 28 VDC sense voltage

to multiplex controller. When connecting D+

terminal to controller through a relay, the

relay coil must be diode protected and rated

for proper voltage. Torque M6 terminal nut

on regulator to 4.5 Nm/40 lb. in.

• Connect P terminal to tachometer or relay.

P terminal taps AC voltage, typically half

the charge voltage. Torque M6 terminal nut

on regulator to 4.5 Nm/40 lb. in.

Note: If you are replacing an A2-205 regulator with
an A2-213 regulator, make sure you connect the
existing R terminal lead to the P terminal on the
A2-213. The remaining D+ terminal on the A2-213
will not have a connecting cable.

If you are replacing an A2-207 regulator with an
A2-213 regulator, make sure your connect the
existing D+ terminal lead to the D+ terminal on
the A2-213. The remaining P terminal on the
A2-213 will not have a connecting cable.

6. LED operation modes:

• Green lens LED will light STEADY when

regulator is energized and functioning properly.

• Green lens LED will FLASH once every five

seconds when regulator is energized and engine

is not running.

• Green lens LED will not be lit when regulator

is not energized.