ClimaCool Electrical Data - 60 HZ

NOTES:

1. RLA. Rated Load Amps are calculated as per UL1995.
2. MCA. Minimum Circuit Ampacity: 125% of the RLA of the largest compressor motor plus 100% of the RLA (or FLA) of all

other concurrent motors and/or electrical loads.

3. MOP. Maximum Overcurrent Protection or Max.Fuse Sizing: Rounded down from 225% of the RLA of the largest compressor

motor plus 100% of the RLA (or FLA) of all other concurrent electrical loads.

4. Recommended (Dual Element) Fuse Sizing: Rounded up from 150% of the RLA of the largest compressor motor plus 100% of

the RLA (or FLA) of all other concurrent electrical loads.

5. Locked Rotor Amps are instantaneous starting amperage per compressor.
6. Module internal wiring is per NEC.
7. Voltage Tolerance Range:

208-230V / 60Hz: Min. 187V Max. 253V
460V / 60Hz: Min. 414V Max. 506V
575V / 60Hz: Min. 518V Max. 632V

8. MOP Device or Recommended Fusing Device for Module Power Wiring supplied by others.

These are recommended values for electrical power protection of modules selected.

LEGEND:

RLA

-

Rated Load Amps

LRA

-

Locked Rotor Amps

MCA

-

Minimum Circuit Amps

MOPD -

Maximum Overcurrent Protection Device

Model Voltage Power Wiring - per Module Internal Wiring - per Compressor

FLEX RLA

1

MCA

2

MOP

3,8

Rec. Fuse

4,8

RLA

1

MCA

2

LRA

5

Fuse Size

4

208-230/3/60

92

103

125

125

46

58

425

70

30

460/3/60

42

47

60

60

21

26

187

35

30

575/3/60

33

37

50

45

17

21

148

30

50

208-230/3/60

142

160

225

200

71

89

500

110

50

460/3/60

64

72

100

90

32

40

250

50

50

575/3/60

51

58

80

70

26

32

198

40

65

208-230/3/60

183

206

250

250

92

115

600

150

65

460/3/60

83

93

125

110

41

52

310

70

65

575/3/60

66

75

100

90

33

41

255

60