CHILLER OPERATION AND MAINTENANCE

Pressure and Temperature Log
A log of temperatures and pressures should be taken
regularly. Periodically conduct a visual inspection
of the chiller to identify problems before they reach
the point of failure. As with any mechanical system,
it is necessary to conduct a series of checks to the
ClimaCool chiller to confirm correct operation.

Daily
• A daily operational log should be kept
• Perform visually inspection
• Record entering and leaving chilled water and

condenser water temperatures and pressures

• Note any problems that may exist. Immediately

plan for further investigation. If repair is necessary,
schedule for earliest possible date.

• Properly document all data taken

Weekly
• Review daily log from previous week
• Perform visual inspection
• Properly document all data taken
• Note any problems that may exist. Immediately plan for

further investigation. If repair is necessary, schedule for
earliest possible date.

Quarterly
• Check controller operating parameters and set points
• Check refrigerant pressures and temperatures
• Check compressor amps
• Check compressor oil level
• Check and test all safeties
• Check water flow rates and pressure drops across

evaporator and condenser

• Properly document all data taken

Annual
• Isolate chiller, drain all water circuits
• Back flush all heat exchangers (use only ClimaCool

recommended de-scalers)

• Remove and clean all waterside strainers
• Perform leak test on all refrigerant circuits
• Check all interconnecting flanges for proper

tightness

• Perform oil analysis on each compressor
• Check and test all refrigerant safeties for proper operation
• Check all electrical terminal connections for tightness
• Manually operate all waterside isolation valves on each

module

• Check all peripheral systems for proper operation
• Check and test main controller
• Verify set points, sensors and general configuration
• Properly document all data taken

HEAT EXCHANGERS

Back Washing
It may become evident from the recorded daily log data that
the performance of the chiller is gradually degrading. This
could be due to a buildup of debris or sludge obstructing the
free passage of flow through the heat exchangers. This debris
can be removed by a "back washing" process, which involves
the introduction of a forced, violent, backwards flow through
the heat exchanger, using a carefully formulated flushing
solution. To be effective, this back flow should be slightly

Chiller Operation and Maintenance

1


www.climacoolcorp.com

Recommended Maintenance Schedule

Pressure and Temperature Log

A log of temperatures and pressures should be taken regularly. Periodically conduct a visual inspection of the chiller to
identify problems before they reach the point of failure. As with any mechanical system, it is necessary to conduct a
series of checks to the ClimaCool

®

chiller to confirm correct operation.

Maintaining a Daily Log

Date _______

Data Log ___________________

Chiller No.
______

Technician
___________________

Sun. Mon. Tue. Wed. Thu. Fri. Sat.

Chilled Water

Entering Temp.

Chilled Water

Leaving Temp.

Condenser Water

Entering Temp.

Condenser Water

Leaving Temp.

Chilled Water

Pressure Drop

Condenser Water

Pressure Drop

Faults: Note By

Module Number

Daily

A daily operational log should be kept

Perform visually inspection

Record entering and leaving chilled water and
condenser water temperatures and pressures

Note any problems that may exist. Immediately
plan for further investigation. If repair is
necessary, schedule for earliest possible date.

Properly document all data taken


Weekly

Review daily log from previous week

Perform visual inspection

Properly document all data taken

Note any problems that may exist.
Immediately plan for further investigation. If
repair is necessary, schedule for earliest
possible date.

Quarterly

Check controller operating parameters and set
points

Check refrigerant pressures and temperatures

Check compressor amps

Check compressor oil level

Check and test all safeties

Check water flow rates and pressure drops
across evaporator and condenser

Properly document all data taken

Annual

Isolate chiller, drain all water circuits

Back flush all heat exchangers (use only
ClimaCool

®

recommended de-scalers)

Remove and clean all waterside strainers

Perform leak test on all refrigerant circuits

Check all interconnecting flanges for
proper tightness

Perform oil analysis on each compressor

Check and test all refrigerant safeties for
proper operation

Check all electrical terminal connections for
tightness

Manually operate all waterside isolation valves
on each module

Check all peripheral systems for proper
operation

Check and test main controller

Verify set points, sensors and general
configuration

Properly document all data taken