1.

Connect to isolated battery terminals only

2.

Make good connection RED +, BLACK -

3.

All LEDs should indicate in sequence before commencing test

4.

Provided power is available in battery under test, a flashing YELLOW LED will indicate

battery load test in progress

5.

Latched RED LED indicates battery under test has failed

6.

Latched GREEN LED indicates battery under test has passed

7.

If required, test twice in succession only to simulate a 3 hour load test, leaving 30%

minimum capacity available in the battery

NOTE: When flashing RED LED indicates, allow battery tester 5 minutes to cool down

IMPORTANT: Only use test leads provided (Part: CD4000TL) Replace polarity protection fuse

with 10Amp blade type only

CD4000

Luminaire Battery Tester

Simulates a 1 hour battery load test in under 6 minutes

Tests all 2.4 - 12V rechargeable batteries above 1.5AH

FAIL

TESTING

PASS

Operating Instructions

CD4000

Luminaire Battery Tester

Take minutes not hours to test luminaire batteries used in stand-alone
emergency lighting systems. The CD4000 performs 1 and 3 hour duration
tests in minutes on 2.4V - 12V rechargeable Lead-acid, Lithium-ion, Nickel-
cadmium and Nickel Metal Hydride batteries.

Meters Ltd

www.actmeters.com

+44(0)1744 886660

Input Sockets

RED + BLACK -

Test Leads

2m long, heavy duty leads with crock clips

(ACT CD4000TL)

Power Supply

Self powered by the battery under test

(step-up inverter)

LED Indication

RED/Fail YELLOW/Testing GREEN/Pass

Acceptable Batteries

2.4V to 12V SLA, LI-ION, NICAD & NIMH

Minimum Battery Capacity

Greater than 1.5Ah

Current Drawn During Test

0.5Amp

Test Times

Normally under 6mins dependant on

battery voltage

Heat Dissipation

Between 23 to 115 watts

Ambient Operating Temperature

-5 to 40C

Maximum Heatsink Temperature

(Safety Trip Point)

100C

Input Protection

Reverse polarity and high voltage protection

(18VDC Max)

Input Fuse

10Amp quick blow blade type

Enclosure

Flame retardant plastic

Size

167mm x 107mm x 65mm

Weight

1.5kg

Specifications

2004/108/EC

CALINST/0213

ACT Meters Ltd

The Old Smithy

Church Road

Rainford

Merseyside

WA11 8HD

United Kingdom