3 control panel k3, 2 changing the settings, 1 control panel b3 – DE DIETRICH DTG 330 User Manual

Page 8: Control panel k3, Control panel b3

Advertising
background image

8

DTG 330

15/12/08 - 300011852-001-C

4. Operating the appliance

4.1.3

Control panel K3

1. General ON (1) / OFF (0) switch

2. Burner alarm indicator + Reset button

This light comes on when the safety control box is in safety
lockout (out of order).

3. Switch AUTO/

!

/TEST-STB

AUTO: This position enables automatic operation of the
installation in accordance with DIEMATIC-m 3 regulation
controls.

!

: The boiler no longer takes orders from the DIEMATIC-m 3

regulation into account. The boiler is regulated by the boiler
thermostat(s).
TEST-STB: Temporary action to test the safety thermostat

4. Safety thermostat with manual reset

Set at 110° C

5. Timed circuit breaker (4 A)

6. Pump shutdown switch

7. Boiler thermostat (30 to 90 °C)

8. Boiler thermometer

9. Switch for selecting the number of burner stages

(2-stage boilers)

10. Connector USB

4.2 Changing the settings

4.2.1

Control panel B3

Heating temperature setting: Set the boiler thermostat to the
desired setting.
Setting the domestic hot water temperature: Set the DHW
thermostat to the desired setting.