Technical data

Typ 2300

Pilot pressure for control function B

Actuator
size

Connection
size [mm]

Pilot pressure [bar]

Max. per-
mitted
medium
pressure
[bar]

for medium pressure

0 bar

max

ø 50 mm

15

4.6

6.6

16

20

5.1

7.0

9

25

5.1

7.0

5

ø 70 mm

15

4.4

5.3

16

20

5.2

6.8

16

25

5.2

7.0

12

32

5.2

7.0

6

ø 90 mm

25

2.4

4.2

16

32

2.4

5.3

16

40

2.5

6.5

16

50

2.5

7.0

14

ø 130 mm

40

2.7

4.5

16

50

2.7

5.6

16

65

2.7

7.0

16

Tab. 4: Pilot pressure for control function B

The required minimum pilot pressure P

min

with control function B and

I (flow below the seat) is dependent on the pressure of the medium.

The pressure diagrams are in the operating instructions on
the Internet:

www.burkert.com

7.5. General technical data

Media
Control medium

neutral gases, air

Flow media

Water, Alcohol, Fuel, Hydraulic liquids,

Saline solutions, Lyes, Organic solvents

Installation position as required, preferably with actuator in

upright position

Protection class

IP67 in accordance with

IEC 529/EN 60529

Control functions (CF) The valve seat is always closed against the

medium flow

Control function A

Normally closed by spring action

Control function B

Normally open by spring action

Control function I

Actuating function via reciprocal pressur-
ization (not for actuator size ø 50 mm in
combination with Type 8696)

8. INSTALLATION

8.1. Safety instructions

DANGER!

Danger – high pressure in the equipment!
• Before loosening the lines and valves, turn off the pressure and

vent the lines.

english