Burkert Type 6213 User Manual

Burkert Accessories for water

Advertising
background image

en / de / fr

english

Type 6213
PD22

Additional information on safety shut-off device for combustion
installations according to DIN EN ISO 23553-1

Zusatzinformation Sicherheitsabsperreinrichtung für
Feuerungsanlagen nach DIN EN ISO 23553-1

Information complémentaire concernant le dispositif d’arrêt de
sécurité pour installations de chauffage selon DIN EN ISO23553-1

© 2013 Bürkert Werke GmbH
Supplement 1302/00_EU-ml_00809448 / Original DE

Basic safety instructions

These safety instructions do not make allowance for any:
• Contingencies and events which may arise during the installation,

operation and maintenance of the devices.

• Local safety regulations – the operator is responsible for observing

these regulations, also with reference to the installation personnel.

risk of injury due to impaired function after external fire!
• After an external fire, check the equipment and safety shut-off

device.

• If there is visible damage, replace shut-off device!

technical Data

Material
Body:

Brass

Seat seal:

FKM (F)

Body seal:

FKM (F)

Coil jacket:

Epoxy or Polyamide

Media

Heating oils DIN 51603 Part 1 or diesel fuel acc. to DIN EN

590 with viscosity 1.6 – 21 cST (other media requires a prior

agreement with the Bürkert sales office)

Medium temperature

0 ... 90 °C

Ambient temperature

0 ... 60 °C

Protection class

IP65 in accordance with EN

60529 with correctly connected

and installed cable plug, Bürkert

Type 2508 in accordance with DIN

17503-803

installation

Dirt filter:
• For orifices DN 10 to DN 40

A dirt filter (≤ 500 μm) must be installed before the valve inlet.

Note!

Pipelines soiled with sealing material may cause a

malfunction!
• Do not seal pipe connections with hemp or PTFE tape.

electrical connection of the caBle Plug

The safety shut-off devices for combustion installations may be

operated only with the Bürkert device socket type 2508.

Authorized cable plug Bürkert
Type 2508

max. 1 nm

Seal

Malfunctions

After occurrence of an external fire:
• After an external fire, check the equipment and safety shut-off

device.

• If there is visible damage, replace shut-off device!

oPerating PrinciPle / WirkungsWeise / MoDe
D’action

A

(NC)

P

A

2/2-way valve, normally closed.
2/2-Wege Ventil, stromlos geschlossen.
Vanne 2/2 voies, normalement fermée.

tyPe laBel / tyPschilD / Plaque signalétique

Observe the voltage, current type, and pressure specified

on the type label.
Die auf dem Typenschild angegebene Daten für Spannung,

Stromart und Druck beachten.
Observer les données indiquées sur la la plaque signalétique

pour la tension, le type de courant et la pression.

Body material / Gehäusewerkstoff /

Matériau du corps

Seal material / Dichtwerkstoff /

Matériau du joint

Orifice / Nennweite / Diamètre

nominal

Voltage, Frequency, Power consumption /

Spannung, Frequenz, Leistung / Tension,

fréquence, puissance

Connection thread, Pressure / Anschluss-

gewinde, Nenndruck / Filetage de raccor-

dement, pression nominale

Operating principle

/ Wir-

kungsweise / Fonction

Type / Typ / Type

Register number / Registernummer / Numéro

d‘enregistrement

XXXX

0

XX W

DIN certification mark / DIN Zertifizierungs-

zeichen / Symbole de certification DIN

Register number /

Registernummer /

N° d‘enregistrement

Max. permitted medium temperature / Max. zulässige
Mediumstemperatur / Temp. de fluide max. admissible

XXXX

CE0036

Heizöl DIN 51603 EL, Dieselkraftstoff

max. Mediumstemp. 90 °C
Schutzart IP65 (DIN 40050)

Inspection body / Überwachungs-
stelle / Organisme de survillance

Protection class / Schutzart /
Type de protection

Permitted heating oil grades acc. to DIN 51603 EL and
permitted diesel fuel acc. to DIN EN 590 / Zulässige
Heizölsorten nach DIN 51603 EL und Dieselkraftstoff
nach DIN EN 590 / Qualités de mazout autorisées selon
DIN 51603 et diesel autorisé selon DIN EN 590

Advertising