11 device status/troubleshooting, 1 display of the device status – Burkert Type 8741 User Manual

Page 32

Advertising
background image

32

Devicestatus/Troubleshooting

Type 8741

11

Device sTaTUs/TroUBleshooTinG

11.1 Display of the device status

The MFM/MFC has an LED to display the device status, the colour and status change according to NAMUR 107.
If more than one device status exists simultaneously, the device status with the highest priority is displayed.

led acc. to ne 107

description

What to do?

OFF

The device is not energized.

Energize the device.

Flashing
(any colour)

Device is selected using the "Bürkert Communicator"
software.

Deselect the device in the Communicator.

White / Lit

The device is energized and in a control mode (see
chap. "9.6.3").
A CANopen/ büS communication is established. In the
case of a büS device, an assigned büS peer has been
found.

-

White / Flashing

Mode 1:
Control loop disabled, direct specification of the variable
to the valve.

-

Mode 2:

SETPOINT SOURCE

set to

STORED

SETPOINT

-

Mode 3:
If a CANopen communication is established, the device is
in a Pre-operational Mode or in a Stopped Mode.

-

Red / Lit

Mode 1: faulty sensor.

Maintenance is needed –
Contact the manufacturer.

Mode 2: faulty memory.

Mode 3: faulty device.