TROUBLESHOOTING

Verify that the wiring is correct. Contact FCI Technical Service if problems still persist. The Telephone Number is 1 800 854-1993, or
(760) 744-6950.

GENERAL SPECIFICATIONS

Material of Construction:

Element; 300 Series Stainless Steel Enclosure; Diecast Epoxy Coated Aluminum.

Operating Temperature:

Flow Element;

Low Temp.

-40 to +350°F (-40 to +177°C) High Temp. to 500 °F (260°C)

Electronics;

-40 to +140°F (-40 to +60°C)

Safety Proof Pressure:

500 psig.

Input Power:

18 - 36 Vdc

Repeatability:

0.5% of reading

Mounting:

Vertical or horizontal

Service:

Air or gas (depends on calibration)

Enclosure Classification:

UL Class 1 and 2, Div 1 & 2, Groups C, D, E, F, G

Approvals:

CE Mark

Notice of Proprietary Rights

This document contains confidential technical data, including trade secrets and proprietary information which are the property of Fluid Components
Intl (FCI). Disclosure of this data to you is expressly conditioned upon your assent that its use is limited to use within your company only (and does
not include manufacture or processing uses). Any other use is strictly prohibited without the prior written consent of FCI.

Visit FCI on the Worldwide Web: www.fluidcomponents.com

1755 La Costa Meadows Drive, San Marcos, California 92069 USA - 760-744-6950 - 800-854-1993 - Fax 760-736-6250

© Copyright 2002 Fluid Components Intl a limited liability company All Rights Reserved

Document Number: 06EN003337 Rev. -

ALARM SWITCH POINT SET-UP

The set point may be adjusted blindly or with a volt meter to see relative flow and establish a reference point.

In RUN MODE:

0-25mA related to flow.
0-10Vout related to temperature.
Green LED on = power on (run mode).
Red LED indicates fail-safe setting.
Red LED ON = relay de-energized on flow (or wet condition) BELOW the alarm set point.
Red LED OFF = relay de-energized on flow (or dry condition) ABOVE the alarm set point.

CALIBRATION MODE:

To enter calibration mode, press both buttons simultaneously once.
Both LED’s will be off.

Use either output to monitor the alarm set point.
0-10Vout represents the Set Point.
0-25mA represents the Set Point.

Press both buttons simultaneously to exit CALIBRATION MODE and toggle the fail-safe mode.
The Green LED is on and the Red LED is either on or off, indicating fail-safe setting as described above.

To change fail-safe setting, press both buttons simultaneously twice.