Fluid Components International GF92 User Manual

Page 5

Advertising
background image

Doc. No. 06EN003321 Rev. -

5

Model GF92 Flowmeter

INSTALLATION, OPERATION AND TROUBLESHOOTING GUIDE

FLUID COMPONENTS INTL

..

Wiring the Flow Element:

Connect a shielded, 8 wire cable between the transmitter and the local enclosure terminal strip as shown below. Be sure
the shield (ground wire) is connected to JP3 GND along with the wire from terminal block terminal 2. Do not connect the
shield to the local enclosure (leave it floating).

Connector JP3

Flow Element Wiring Diagram
(Be sure the jumper is in place
Terminal 2 to terminal 4.)

Local Enclosure Wiring Diagram

Flow Element Wiring Table

Wiring the Output Relays:

The instrument contains two sets of alarm output relays (connectors JP4 Relay Output 1, and JP5 Relay Output 2). They
can be wired by the customer as desired. (NO = Normally Open, NC = Normally Closed, Pole = Common)

Output Relay Wiring Diagram

Connectors JP5 and JP4

Flow Elem e nt

Tra nsm itte r

Te rm ina l Block

JP3 (Te rm ina l No.)

Terminal 5 (ACT)

ACT SEN (4)

Terminal 5 (ACT)

ACT EXC (6)

Terminal 4 (GND SEN) GND SEN (2)
Terminal 3 (REF)

REF SEN (3)

Terminal 3 (REF)

REF EXC (5)

Terminal 2 (GND)

GND (1)

Terminal 1 (HTR)

HTR EXC (7)

Terminal 1 (HTR)

HTR SEN (8)

Advertising