INSTALLATION

ST100 Series Flow Meter

14

Fluid Components International LLC

Figure 16

Connection

10 FT

50 FT

100 FT

250 FT

500 FT

1000 FT

Power AC or DC

22

22

22

20

18

16

Flow Element

(8 Conductor Shielded)

24

24

24

22

22

18

STP Flow Element

(10 Conductor Shielded)

22

22

22

22

22

18

Analog Out (HART)

16-30

16-30

16-30

16-30

16-30

16-30

Digital Out

Foundation Fieldbus

FF-844 H1 (14-30 AWG)

Modbus

RS485 (14-30 AWG)

Instrument Wiring Table 1 - Recommended AWG

Analog output maximum load: 600 ohms
Instrument Power Requirements: See Instrument Specifications, page 8.
Instrument Fuse rating and part no:

AC Input Power (85 - 265 Vac):
MFR - LITTLEFUSE, 2A TR5 SLO-BLO series 383 (2 Amp rating), part no. 38312000000; FCI part no. 022499-01.
DC Input Power (24 Vdc):
MFR - LITTLEFUSE, 2A TR5 SLO-BLO series 383 (2 Amp rating), part no. 38312000000; FCI part no. 022499-01.

The input power fuse is located on the customer interface board, see figure 16. Instrument power must be turned off when

replacing the fuse. To replace the fuse, unscrew the clear fuse cover and pull the fuse straight out of the holder. Replace the fuse

with the recommended fuse listed above by aligning the fuse pins with the receiving holes located in the fuse holder and pushing

securely into place until the fuse bottoms in the holder. Replace the fuse cover.