Duct High Limit Humidistat

Application

For low or line voltage on-off control of humidifiers,

dehumidifiers, valves, solenoids valve compressors, relays, etc.

Specifications

Control Dial Settings: 15 to 95% RH.

Humidity Sensing Element: Nylon ribbon.

Differential: 5% RH.

Environment:

Ambient Temperature Limits,

Shipping & Storage -40 to 140

O

F

Operating 40 to 125

O

F

Humidity, 5 to 95% RH, non-condensing.

Location, NEMA 1, indoor locations only.

Electrical Switch: Snap-acting SPDT (see Fig. 1)

Ratings, (See Table 1)

Connections: Coded screw terminals.

Cover: Metal.

Mounting: The outside surface of the return air duct.

Dimensions: 4 ¾” X 6 ½” X 3 ½” (see Fig.2)

Ta ble 1. Maximum Electrical Ratings

AC V olt

50/60 Hz

FLA

LRA

Resistive

Amps

Pilot Dudy

VA

24

-

-

8

60

120

7.2

43.2

8

345

240

3.6

21.6

8

345

Mounting

Mount the H C -20 1 on the outside surface of the return air duct in

a horzontal position where it is exposed to freely circulating air.

CAUTION!

Avoid locations where excessive moisture, corrosive fumes,

vibration or high ambient temperatures are present .

T ypical Installation

1.

2.

Drill the four mounting holes as indicated on Figure 2.

using a 1/8” drill.

3.

Cut out center portion of ducts outlined on template.

4.

Using four (4 ) mounting screws, mount

humidistat to the duct.

5.

Remove the cover and make all electrical connections

in accordance with job wiring diagram and in

compliance w ith nation and local electrical codes (see Fig.3).

6.

Replace the cover.

Turn dial knob to desired setting. If locked dial setting

is desired, remove dial knob, tighten the dial lock

screw and replace knob.

5 1/2”

5 15 /16”

3 3/4”

4 1/4”

4 3/16”

Figure 2. Template Dimensions

6 1/2

4 3/4

Front View

Side View

Figure 1 HC -201 Dimensions

2 1/4

3/4

1 1/4

2 13 /16

Dimensions in inches

Micro Switch Terminals

Figure 3. Connect Humidifier To

ORNAnd BRNTerminals.

ORN

BRN RED