The pump can be mounted to a wall as shown in
Figure D. A wall mount bracket kit is available which
includes all necessary hardware to mount the pump
to the wall. Mounting the pump other than as shown
in Figure D defeats the purpose of the housing drain.
Mounting dimensions for the pump are provided in
Figure F for reference.

4.

The pump can be mounted on top of a solution tank as
shown in Figure E. Install chemical pump on the
cover. Insert suction tubing through the center hole and
cut tubing so foot valve/strainer hangs about 1 or
2 inches (2.5 - 5 cm) above the bottom of the tank.
Mount the chemical pump rigidly by drilling four .25"
(6.3 mm) holes and using four #10 screws and nuts.

5.

USE AN ANTI-SIPHON VALVE IN THE DISCHARGE LINE whenever the fluid pressure in the discharge line
is below atmospheric pressure. This can occur if the injection point is on the suction side of a water pump
or against a "negative" head such as when feeding down into a well, SEE FIGURE G1.