4.

Unstable behavior; non-steady state in control loop.

Possible Causes

Remedies

A. Amplification too high

A1. Reduce amplification.

B. Gland friction on the valve too high

B1. Loosen gland packing somewhat or replace.

5.

Stroke range cannot be adjusted.

Possible Causes

Remedies

A. Wrong range spring

A1. Replace range spring (See Section IV.D.).

B. Positioner does not completely reduce

B1. Check supply air pressure.

pressure

B2. Check amplification.
B3. Adjust clearance between nozzle and flapper.

6.

Positioner makes “buzzing” noise

Possible Causes

Remedies

A. Wrong action setting

A1. Check position of the bypass switch and the action.

Change as required.

REPAIR PARTS KITS

KIT A: Includes gaskets, O-rings and small parts. Order P/N 295-08-5-07410-00.

KIT B: Replacement pneumatic amplifier. Order P/N 653-75-5-09542-00.