Cashco C-PRV User Manual

Model c-prv, Pressure reducing regulator

Advertising
background image

INSTALLATION, OPERATION & MAINTENANCE MANUAL

IOM-C-PRV
12-13

MODEL C-PRV

PRESSURE REDUCING REGULATOR

SECTION I

I. DESCRIPTION AND SCOPE

Model C-PRV is a pressure regulator used to control downstream (outlet or P

2

) pressure. Inlet and outlet sizes

are 1", 1-1/2", 2" and 3" with Tri-Clamp

®

fi tting connections. This regulator is only suitable for liquids and gases at

temperatures less than 300°F (149°C). Refer to Technical Bulletin C-PRV-TB for specifi c design con di tions.

SECTION II

II. INSTALLATION

A. General:

1. An inlet block valve should always be installed

up stream of the regulator.

2. An outlet pressure gauge should be located

ap prox i mate ly ten pipe diameters down stream

and within sight.

3. All installations should include a downstream

re lief device if the inlet pressure could exceed

the pressure rating of any downstream equip-

ment.

4. Flow Direction: Install so fl ow enters through

the bottom connection and exits the side con-

nection.

5. Install with spring chamber (2) in the vertical

up position to allow for proper draining.

A. General:

1. Ensure that lock-open pin (10) and hitch pin

(15) are in proper po si tion. See Sec tion VII.

2. Confi rm that the proper range spring is in di -

cat ed to be within the regulator by inspection
of the unit’s nameplate. Apply setpoint pres-
sures that are only within the stated range.

SECTION IV

IV. START-UP

III. PRINCIPLE OF OPERATION

A. General:

1. Movement occurs as pressure vari a tions reg is-

ter on the di a phragm. The registering pres sure
is the outlet, P

2

or downstream pres sure. The

range spring op pos es diaphragm move ment.
As the outlet pressure drops, the range spring
pushes the diaphragm down, opening the port;

as outlet pressure increases, the diaphragm
pushes up and the port opening closes.

2. A complete diaphragm failure will cause the

reg u la tor to fail open

SECTION III

CAUTION

Installation of adequate overpressure pro tec tion is
recommended to pro tect the reg u la tor from overpres-
sure and all down stream equip ment from damage
in the event of regulator failure.

CAUTION

The Model C-PRV should never be used as a shutoff
device.